Zero-Clearance (Metal) Fireplace Requirements; Face Dimensions; Drafting Performance - Travis Industries Flush Wood Plus Owner's Manual

Flush wood plus insert
Hide thumbs Also See for Flush Wood Plus:
Table of Contents

Advertisement

10
Fireplace Insert Installation

Zero-Clearance (Metal) Fireplace Requirements

Must utilize a positive (full reline) or direct connection (block-off plate)
Must be manufactured by one of the following manufacturers:
• Marco
• Majestic
• Heat N Glo
Entire fireplace, including chimney, must be clean and undamaged. Any damage must be repaired
prior to installation of the insert
Entire fireplace, including chimney, must meet local building requirements
Chimney height: 15' (4.5M) minimum; 33' (10M) maximum (measured from base of insert). Minimum
cross section: 28.65 square inches (18626 sq mm)
The damper ("
A
baffles ("
"), screen ("
D
masonry lining ("
frame, face of the fireplace, etc. – "

Face Dimensions

Avalon Victorian Lace
33"

Drafting Performance

This appliance relies upon natural draft to operate. External forces, such as wind, barometric pressure,
topography, or factors of the home (negative pressure from exhaust fans, chimneys, air infiltration, etc.),
may adversely affect draft. Travis Industries can not be responsible for external forces leading to less
than optimal performance.
© Travis Industries
• Heatilator
• Lennox
• Martin
") and grate ("
") must be removed (see Figure 4). The smoke shelf ("
B
"), and metal or glass doors ("
E
"), insulation ("
"), and any structured rigid frame members (metal sides, floor, door
G
H
") may not be removed or altered
I
H
F
E
23-1/4"
(for qualified installers only)
• Preway
• Tempco
• Monesson
") may be removed (if applicable). The
F
A
C
I
B
Fireplace Xtrordinair Arched
33-3/8"
2-7/8"
51-1/2"
Radius
23-7/8"
100-01269
• Superior
"), internal
C
D
G
Lopi Wilmington
33-1/2"
Figure 4
23-1/4"
Figure 5
4110712

Advertisement

Table of Contents
loading

Table of Contents