Masonry & Zero Clearance Fireplaces; Floor Protection; Minimum Opening For Masonry & Zero Clearance Fireplaces - Quadra-Fire MTVI-E2-MBK Installation Manual

Mt. vernon e2 insert
Hide thumbs Also See for MTVI-E2-MBK:
Table of Contents

Advertisement

Built-In Vertical
J
K
Figure 9.1
The maximum mantel depth (J) is 12 inches (305mm) with a
minimum vertical height (K) of 12 inches (305mm).
However if your mantel has a depth of 10 inches (254mm)
then the vertical minimum height is 10 inches (254mm).
C. Masonry & Zero Clearance Fireplaces
A
E
Figure 9.2
Location
A
Insert side to combustible side wall
B
Insert top to max. 2-1/4 inch face trim
C
Insert side to max. 2-1/4 inch face trim
** Face Trim not to exceed 3/4"
August 3, 2015
3 in
[76mm]
Outside
Air
Mantel
B
C
D
Inches
Millimeters
6
0
0
D. Floor Protection
D
Floor protection hearth extension from
door opening
E
Floor protection to the side of door
opening
Use a non-combustible fl oor protector, extending beneath
appliance and to the front, and sides as indicated.
If employing a hearth extension, any parts or materials used in
construction must be non-combustible.
E. Minimum Opening for Masonry & Zero
Clearance Fireplaces
Figure 9.3
Location
F
Rear Width
G
H
Height
I
Front Width
2-1/4
152
0
0
7082-131J
MT VERNON E2 INSERT
Location
H
G
F
I
Inches
24
Depth
16-1/2
23-7/8
34
Inches
Millimeters
6
152
6
152
Millimeters
610
381
606
864
9