Mitsubishi Electric FR-A701 Instrucion Manual page 80

Hide thumbs Also See for FR-A701:
Table of Contents

Advertisement

(2) Setting
1) Select the advanced magnetic flux vector control, real sensorless vector control or vector control.
2) Set "1" or "101" in Pr. 96 Auto tuning setting/status .
When the setting is "1" . . . . . . . . Tuning is performed without motor running.
·
· When the setting is "101" . . . . . . Tuning is performed with motor running.
3) Set the rated motor current (initial value is rated inverter current) in Pr. 9 Electronic thermal O/L relay.
4) Set the rated voltage of motor (initial value is 200V/400V) in Pr. 83 Rated motor voltage and rated frequency of motor
(initial value is 60Hz) in Pr. 84 Rated motor frequency .
(For a Japanese standard motor, etc. which has both 50Hz and 60Hz rated values, set 200V/60Hz or 400V/60Hz).)
For vector control dedicated motor SF-V5RU1 / V5RU3 / V5RU4, set as the following table.
SF-V5RU1-30kW or less
SF-V5RU1-37kW
SF-V5RU3-22kW or less
SF-V5RU3-30kW
SF-V5RU4-3.7kW, 7.5kW
SF-V5RU4-other than the above
REMARKS
·
When using the vector control dedicated motor SF-V5RU (1500r/min series) or SF-THY, setting 33 and 34 in Pr. 71 selects
internal constants appropriate for dedicated motors. Therefore, Pr. 83 and Pr. 84 settings are unnecessary.
·
Perform auto tuning for SF-V5RU (except for 1500 r/min series) with setting 13 or 14 in Pr. 71 ( For perform auto tuning, set
Pr. 83 and Pr. 84)
5) Set Pr. 71 Applied motor according to the motor used.
Mitsubishi standard motor
Mitsubishi high efficiency motor
Mitsubishi constant-torque motor
Vector control dediated motor
Other manufacturer's
standard motor
Other manufacturer's
constant torque motor
* For other settings of Pr. 71, refer to chapter 4 of
It takes approximately 25 to 120s
(Excitation noise is produced during tuning.)
*Tuning time differs according to the inverter capacity and motor type.
It takes approximately 40s until tuning is completed.
The motor runs at nearly its rated frequency.
Pr. 83 Setting
160V
170V
160V
170V
150V
160V
Motor
SF-JR
SF-HR
Others
SF-JRCA 4P
SF-HRCA
Others (SF-JRC, etc.)
SF-V5RU (1500r/min series)
SF-THY
SF-V5RU (except for 1500r/min series)
the instruction manual (applied).
Before operation
until tuning is completed.
*
Pr. 84 Setting
33.33Hz
16.67Hz
Pr. 71 Setting
*
3
43
3
13
53
13
33
13
3
13
4
73