Parameter List
Parameter
RUN terminal
190
function selection
SU terminal
191
function selection
IPF terminal
192
function selection
OL terminal function
193
selection
FU terminal function
194
selection
ABC1 terminal
195
function selection
ABC2 terminal
196
function selection
232 to 239
Refer to Pr. 4 to Pr. 6.
240
Refer to Pr. 72.
241
Refer to Pr. 125 and Pr. 126.
242, 243
Refer to Pr. 73.
120
Incre
Initial
Name
ments
Value
1
0
1
1
1
2
1
3
1
4
1
99
1
9999
Range
Description
0, 100: Inverter running
0 to 6, 8,
1, 101: Up to frequency
10 to 20,
2, 102: Instantaneous power failure/
25 to 28,
undervoltage
30 to 36, 39,
3, 103: Overload alarm
41 to 47,
4, 104: Output frequency detection
64, 70, 84,
5, 105: Second output frequency detection
90 to 99,
6, 106: Third output frequency detection
100 to 106,
8, 108: Electronic thermal relay function
108,
pre-alarm
10, 110:PU operation mode
110 to 116,
11, 111: Inverter operation ready
120,
12, 112:Output current detection
125 to 128,
13, 113:Zero current detection
130 to 136,
14, 114:PID lower limit
139,
15, 115:PID upper limit
141 to 147,
16, 116:PID forward/reverse rotation
164, 170,
output
184,
17, —: Electronic bypass MC1
190 to 199,
18, —: Electronic bypass MC2
9999
19, —: Electronic bypass MC3
20, 120:Brake opening request
25, 125:Fan fault output
26, 126:Heatsink overheat pre-alarm
27, 127:Orientation in-position *
28, 128:Orientation error *
30, 130:Forward rotation output *
31, 131:Reverse rotation output *
32, 132:Regenerative status output *
33, 133:Operation ready 2
34, 134:Low speed output
35, 135:Torque detection
0 to 6, 8,
36, 136:In-position *
10 to 20,
39, 139:Start time tuning completion
25 to 28,
41, 141:Speed detection
30 to 36, 39,
42, 142:Second speed detection
41 to 47, 64,
43, 143:Third speed detection
70, 84, 90,
44, 144:Inverter running 2
91,
45, 145:Inverter running and start command
94 to 99,
is on
100 to 106,
46, 146:During deceleration at occurrence
108,
of power failure (retained until
110 to 116,
release)
120,
47, 147:During PID control activated
125 to 128,
64, 164:During retry
130 to 136,
70, 170:PID output interruption
139,
84, 184:Position control preparation ready *
141 to 147,
90, 190:Life alarm
164, 170,
91, 191:Fault output 3 (power-off signal)
184, 190,
92, 192:Energy saving average value
updated timing
191, 194 to
93, 193:Current average monitor signal
199, 9999
94, 194:Fault output 2
95, 195:Maintenance timer signal
96, 196:Remote output
97, 197:Alarm output 2
98, 198:Alarm output
99, 199:Fault output
9999: No function
0 to 99: Positive logic
100 to 199: Negative logic
* Available only when used with the FR-A7AP.