Delivery, Storage, And Handling; Project Conditions; Operating Characteristics; Electrical Requirements - Carrier WeatherMaster 50HCQ Product Data

High efficient packaged rooftop units 3 to 10 tons
Hide thumbs Also See for WeatherMaster 50HCQ:
Table of Contents

Advertisement

14. High Efficient Motors listed shall meet Section 313 of the Energy Independence and Security Act of 2007 (EISA
2007).
23 81 19.13.C.

Delivery, Storage, and Handling

1. Unit shall be stored and handled per manufacturer's recommendations.
2. Lifted by crane requires either shipping top panel or spreader bars.
3. Unit shall only be stored or positioned in the upright position.
23 81 19.13.D.

Project Conditions

1. As specified in the contract.
23 81 19.13.E.
Project Conditions
1. As specified in the contract.
23 81 19.13.F.

Operating Characteristics

1. Unit shall be capable of starting and running at 125_F (52_C) ambient outdoor temperature, meeting maximum
load criteria of AHRI Standard 210/240 or 340/360 at ± 10% voltage.
2. Compressor with standard controls shall be capable of operation down to 30_F (- - 1_C), ambient outdoor temperat-
ures. Accessory Low Ambient controls are available if mechanically cooling at ambient temperatures below 30_F
(- - 1_C).
3. Unit shall be capable of simultaneous heating duty and defrost cycle operation when using accessory electric
heaters.
4. Unit shall discharge supply air vertically or horizontally as shown on contract drawings.
5. Unit shall be factory configured for vertical supply & return configurations.
6. Unit shall be field convertible from vertical to horizontal configuration. No special kits on 04- - 09 sizes. Size 12
model shall require a supply duct kit for field installation.
7. Unit shall be capable of mixed operation: vertical supply with horizontal return or horizontal supply with vertical
return.
23 81 19.13.G.

Electrical Requirements

1. Main power supply voltage, phase, and frequency must match those required by the manufacturer.
23 81 19.13.H.
Unit Cabinet
1. Unit cabinet shall be constructed of galvanized steel, and shall be bonderized and coated with a prepainted baked
enamel finish on all externally exposed surfaces.
2. Unit cabinet exterior paint shall be: film thickness, (dry) 0.003 inches minimum, gloss (per ASTM D523, 60_F):
60, Hardness: H- - 2H Pencil hardness.
3. Evaporator fan compartment interior cabinet insulation shall conform to AHRI Standards 210/240 or 340/360
minimum exterior sweat criteria. Interior surfaces shall be insulated with a minimum 1/2- - in. thick, 1 lb density,
flexible fiberglass insulation, neoprene coated on the air side. Aluminum foil- - faced fiberglass insulation shall be
used in the heat compartment.
4. Base of unit shall have a minimum of three locations for thru- - the- - base electrical connections (factory- - installed or
field- - installed), standard.
5. Base Rail
a. Unit shall have base rails on a minimum of 2 sides.
b. Holes shall be provided in the base rails for rigging shackles to facilitate maneuvering and overhead rigging.
c. Holes shall be provided in the base rail for moving the rooftop by fork truck.
d. Base rail shall be a minimum of 16 gauge thickness.
6. Condensate pan and connections:
a. Shall be a sloped condensate drain pan made of a non- - corrosive material.
b. Shall comply with ASHRAE Standard 62.
c. Shall use a 3/4- - in. - - 14 NPT drain connection, possible either through the bottom or end of the drain pan. Con-
nection shall be made per manufacturer's recommendations.
7. Top panel:
a. Shall be a single piece on all 04 to 09 models. Two piece on size 12 models.
8. Electrical Connections
a. All unit power wiring shall enter unit cabinet at a single, factory prepared, knockout location.
b. Thru- - the- - base capability
(1.) Standard unit shall have a thru- - the- - base electrical location(s) using a raised, embossed portion of the unit
basepan.
92