Table 63 - - MCA/MOCP DETERMINATION WITHOUT C.O. OR UNPWRD C.O. (Cont.)
ELEC HTR
IFM
TYPE
NOM (kW)
---
10.0
16.5
STD
33.5
43.5
50.0
---
10.0
16.5
MED
33.5
43.5
50.0
---
10.0
16.5
HIGH
33.5
43.5
50.0
---
10.0
HIGH
16.5
High
33.5
Eff.
43.5
50.0
See page 64 for Legend and Notes.
WITHOUT P .E.
FLA
MCA
MOCP
---
17.1
20
9.6
29.1
30
15.9
36.9
40
32.2
57.3
60
41.8
69.3
70
48.1
65.2
70
---
17.9
20
9.6
29.9
30
15.9
37.7
40
32.2
58.1
60
41.8
70.1
80
48.1
66.0
70
---
21.2
25
9.6
33.2
35
15.9
41.1
45
32.2
61.5
70
41.8
73.5
80
48.1
69.3
80
---
24.9
30
9.6
36.9
40
15.9
44.7
45
32.2
65.1
70
41.8
77.1
80
48.1
73.0
80
WITHOUT C.O. or UNPWR C.O.
DISC. SIZE
MCA
FLA
LRA
18
95
20.9
29
105
32.9
36
111
40.7
55
127
61.1
66
179
73.1
73
191
69.0
19
106
21.7
30
116
33.7
37
122
41.5
56
138
61.9
67
190
73.9
74
202
69.8
23
109
25.0
34
119
37.0
41
125
44.9
60
141
65.3
71
193
77.3
78
205
73.1
26
118
28.7
37
128
40.7
44
134
48.5
63
150
68.9
74
202
80.9
81
214
76.8
71
WITH P .E. (pwrd fr/unit)
DISC. SIZE
MOCP
FLA
LRA
25
22
99
35
33
109
45
41
115
70
59
131
80
70
183
80
78
195
25
23
110
35
34
120
45
42
126
70
60
142
80
71
194
80
79
206
30
27
113
40
38
123
45
45
129
70
64
145
80
75
197
80
82
209
35
30
122
45
41
132
50
49
138
70
67
154
90
78
206
80
86
218