Convenience Outlet; Thru-The-Base Connectors; Propeller Power Exhaust; Roof Curbs - Carrier WeatherMaster 50HCQ Product Data

High efficient packaged rooftop units 3 to 10 tons
Hide thumbs Also See for WeatherMaster 50HCQ:
Table of Contents

Advertisement

7. Convenience Outlet:

a. Powered convenience outlet.
(1.) Outlet shall be powered from main line power to the rooftop unit.
(2.) Outlet shall be powered from line side or load side of disconnect by installing contractor, as required by
code. If outlet is powered from load side of disconnect, unit electrical ratings shall be UL certified and
rated for additional outlet amperage.
(3.) Outlet shall be factory- - installed and internally mounted with easily accessible 115- - v female receptacle.
(4.) Outlet shall include 15 amp GFI receptacles with independent fuse protection.
(5.) Voltage required to operate convenience outlet shall be provided by a factory- - installed step down trans-
former.
(6.) Outlet shall be accessible from outside the unit.
b. Non- - Powered convenience outlet.
(1.) Outlet shall be powered from a separate 115- - 120v power source.
(2.) A transformer shall not be included.
(3.) Outlet shall be factory- - installed and internally mounted with easily accessible 115- - v female receptacle.
(4.) Outlet shall include 15 amp GFI receptacles.
(5.) Outlet shall be accessible from outside the unit.
8. Thru- - the- - Base Connectors:
a. Kits shall provide connectors to permit electrical connections to be brought to the unit through the unit base-
pan.
b. Minimum of three connection locations per unit.

9. Propeller Power Exhaust:

a. Power exhaust shall be used in conjunction with an integrated economizer.
b. Independent modules for vertical or horizontal return configurations shall be available.
c. Horizontal power exhaust shall be mounted in return ductwork.
d. Power exhaust shall be controlled by economizer controller operation. Exhaust fans shall be energized when
dampers open past the 0- - 100% adjustable setpoint on the economizer control.
10. Roof Curbs (Vertical):
a. Full perimeter roof curb with exhaust capability providing separate air streams for energy recovery from the
exhaust air without supply air contamination.
b. Formed galvanized steel with wood nailer strip and shall be capable of supporting entire unit weight.
c. Permits installation and securing of ductwork to curb prior to mounting unit on the curb.
11. Medium and high Static Indoor Fan Motor(s) and Drive(s) (04- - 12):
a. Medium and high static motor(s) and drive(s) shall be factory- - installed to provide additional performance
range.
12. Thru- - the- - Bottom Utility Connectors:
a. Kit shall provide connectors to permit gas and electrical connections to be brought to the unit through the
basepan.
13. Outdoor Air Enthalpy Sensor:
a. The outdoor air enthalpy sensor shall be used to provide single enthalpy control. When used in conjunction
with a return air enthalpy sensor, the unit will provide differential enthalpy control. The sensor allows the unit
to determine if outside air is suitable for free cooling.
14. Return Air Enthalpy Sensor:
a. The return air enthalpy sensor shall be used in conjunction with an outdoor air enthalpy sensor to provide dif-
ferential enthalpy control.
15. Indoor Air Quality (CO
a. Shall be able to provide demand ventilation indoor air quality (IAQ) control.
b. The IAQ sensor shall be available in duct mount, wall mount, or wall mount with LED display. The setpoint
shall have adjustment capability.
16. Smoke detectors (Factory- - Installed Only):
a. Shall be a Four- - Wire Controller and Detector.
b. Shall be environmental compensated with differential sensing for reliable, stable, and drift- - free sensitivity.
c. Shall use magnet activated test/reset sensor switches.
d. Shall have tool- - less connection terminal access.
e. Shall have a recessed momentary switch for testing and resetting the detector.