System Event Communication Options; Input Supply Fail Tx Delay; Generic Zone Reporting Timer; Number Of Attempts - DSC Skyroute CL3050 ver 1.2 Installation & Programming Manual

Universal wireless communicator compatible with all powerseries keypads
Table of Contents

Advertisement

Skyroute CL3050 Universal Wireless Communicator

[21] System Event Communication Options

NOTE: Section [20], Option [7] must be enabled for these events to be communi-
cated.
Option 1 - Input Supply Failure
If AC power is absent or if DC power drops below 8.8V
terminals, a trouble will be sent after the delay programmed in section [22] has
expired. Default - ON,
Option 2 - Low Battery
If the battery voltage drops below 5.72V
When the battery voltage rises to 5.87V
Default - ON.
Option 3 - Skyroute CL3050 Tamper
Removing the cover on the Skyroute CL3050 will send a tamper reporting code
to Connect 24. Default - OFF.
Option 4 - PC5108 Module Fault
Indicates a Keybus communications fault condition. Default - OFF.
Option 5 - PC5108 Tamper
Removing the cover on the PC5108 will send a tamper reporting code to
Connect 24. Default - OFF.
Option 6 - TLM Trouble Report
Indicates a telephone line trouble if a CL3050 communications zone is violated.
Default - OFF.

[22] Input Supply Fail TX Delay

This value determines the delay (default 0700 = 7 hrs) before an input supply fail-
ure reporting code is sent if programmed. See Section [21], Option [1] and Sec-
tion [20], Option [2]. Default - 0700 (=7 hrs)

[23] Generic Zone Reporting Timer

This hex value determines the delay before a generic zone reporting code is sent,
if programmed in Section 20 Option 8.
NOTE: There are four separate timers for Burglary, Fire, Panic and Supervisory;
the delay programmed is the same for each timer.
Default - 1E (300 seconds / 5 minutes) Range equals 01-FF Hex seconds x 10

[24] Number of Attempts

This value determines how many attempts are made to send an event to
Connect 24.
NOTES: For UL Installations in Mode 2, minimum 5, maximum 10 attempts
required.
For UL Installations in Mode 3, the combination of attempts between DACT and
Skyroute shall be minimum 5 and maximum 10.

[25] Response Wait Time

This value determines how long the Skyroute CL3050 will wait for a response
from Conect 24 before attempting to resend the same event.
Default - FA (250 seconds) range equals 01-FF Hex seconds.
NOTE: For UL Installations this must be 90 seconds (5A).
Default - 03
15
DC
a trouble will be sent to Connect 24.
DC
the system will send a restore.
DC
All Modes
on the RED and BLK
All Modes
All Modes
Mode 3
Mode 3
All Modes
All Modes
Modes 2, 3
All Modes
All Modes