Accessory Usage Guideline - Carrier Performance 12 38YZA Product Data

60 hz heat pump with puron refrigerant sizes 018 thru 060
Table of Contents

Advertisement

THERMOSTAT/SUBBASE PKG
TSTATCCPRH01-B*
TSTATCCPHP01-B
TSTATCCNHP01-B
TSTATCCSHP01
TSTATCCBHP01*
TSTATCCPDF01-B*
TSTATXXSEN01-B**
TSTATXXNBP01†
TSTATXXPBP01†
TSTATXXBBP01†
TSTATXXSBP01
TSTATXXCNV10‡
* Do not use in zoning heat pump applications.
† This plate is designed to cover surrounding wall area located behind thermostat.
‡ Thermostat conversion kit is a 24-vac accessory that can turn a 4-wire thermostat application into a 5-wire application. This kit can also be used to replace
a broken thermostat wire, or add an extra wire when needed.
** Outdoor temperature sensor is an accessory for all Carrier electronic thermostats, except the non-programmable air conditioner version and builder's
thermostats. It allows the temperature at a remote location (outdoors) to be displayed on the thermostat.
The outdoor air temperature sensor must be used with the dual fuel thermostat.
The outdoor air temperature sensor is included with the Thermidistat Control and dual fuel thermostat.

Accessory usage guideline

ACCESSORY
Crankcase Heater
Evaporator Freeze Thermostat
Compressor Start Assist — Capacitor and Relay
Puron Low Ambient Pressure Switch
Wind Baffle
Support Feet
Puron Hard Shutoff TXV
Puron Liquid-Line Solenoid Valve for Heating
* For tubing line sets between 50 and 175 ft and/or 20 ft elevation difference between indoor and outdoor units, refer to the Application Guideline and Service Man-
ual—Air Conditioners and Heat Pumps Using Puron® Refrigerant.
† Required for all applications.
Accessory description and usage (Listed alphabetically)
1. Ball-Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.
Usage Guideline:
Required on all units when MotorMaster®—Low-Ambient Controller is installed.
2. Coastal Filter
A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow.
3. Compressor Start Assist – Capacitor and Relay
Start capacitor and relay gives a "hard" boost to compressor motor at each start up.
Note:
Heat pumps with Puron-refrigerant and a reciprocating compressor have capacitor and relay factory supplied.
Usage Guideline:
Required for single-phase reciprocating compressors in the following applications:
Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Required for single-phase scroll compressors in the following applications:
Long line
Low ambient cooling
Suggested for all compressors in areas with a history of low voltage problems.
4. Compressor Start Assist — PTC Type
Solid state electrical device which gives a "soft" boost to the compressor at each start-up.
Usage Guideline:
Suggested in installations with marginal power supply.
5. Crankcase Heater
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on
restart and minimizes the chance of liquid slugging.
Note:
Some heat pumps are factory supplied with a crankcase heater. See accessory list for units that come standard with a crankcase heater. For units that do
not, use the guideline below.
Usage Guideline:
Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.
Thermidistat™ Control — Non-Programmable/Programmable Thermostat with Humidity Control
(For use in Dual Fuel, AC, HP, and 2S applications. Includes Outdoor Air Temperature Sensor.)
Thermostat — Auto Changeover, 7-Day Programmable, °F/°C, 2-Stage Heat/1-Stage Cool
Thermostat — Auto Changeover, Non-Programmable, °F/°C, 2-Stage Heat/1-Stage Cool
Standard Programmable Thermostat—Manual Changeover, 5-2 Day Programmable, °F/°C,
1-Stage Heat/1-Stage Cool
Builder's Thermostat — Heat Pump, Non-Programmable, °F/°C, 2-Stage Heat/1-Stage Cool,
Manual Changeover
Dual Fuel Thermostat — Auto Changeover, 7-Day Programmable, °F/°C, Includes Outdoor Sensor
(TSTATXXSEN01-B)
Outdoor Air Temperature Sensor
Backplate for Non-Programmable Thermostat
Backplate for Programmable Thermostat and Thermidistat™ Control
Backplate for Builder's Thermostat
Backplate for Standard Programmable Thermostat
Thermostat Conversion Kit (4 to 5 Wire) — 10 Pack
REQUIRED FOR LOW-AMBIENT
APPLICATIONS
(BELOW 55°F)
See Low-Ambient
Pressure Switch Instructions
Recommended
DESCRIPTION
Yes
Yes
Yes
Yes
Yes†
No
See Long-Line Application Guideline
REQUIRED FOR LONG-LINE
APPLICATIONS*
(OVER 50 FT)
Yes
No
Yes
No
No
No
Yes†
5

Hide quick links:

Advertisement

Table of Contents
loading