Adjustments; Set Gas Input Rate - Payne PG9MAB Series A Installation Manual

4-way multipoise fixed-capacity dual-vent condensing gas furnace sizes 040 thru 140 series a
Hide thumbs Also See for PG9MAB Series A:
Table of Contents

Advertisement

To Begin Component Self-Test:
WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in electrical shock, personal injury, or death.
Blower access panel door switch opens 115-v power to control center. No component operation can occur. Caution must be taken
when manually closing this switch for service purposes.
1. Remove blower access door.
2. Disconnect the thermostat R lead from furnace control.
3. Manually close blower door switch.
4. For approximately 2 sec, short (jumper) the C
until the LED goes out. Remover jumper from terminals. (See Fig. 35.)
NOTE: If TEST/TWIN and C
retrieval request.
Component test sequence is as follows:
a. LED will display previous status code 4 times.
b. Inducer motor starts and continues to run until Step f of component test sequence.
c. After 7 seconds the hot surface igniter is energized for 15 sec, then off.
d. Blower motor operates on HEAT speed for 10 sec.
e. Blower motor operates on COOL speed for 10 sec.
f. Inducer motor stops.
5. Reconnect R lead to furnace control, remove tape from blower door switch, and re-install blower door.
6. Operate furnace per instruction on outer door.
7. Verify furnace shut down by lowering thermostat setting below room temperature.
8. Verify that furnace restarts by raising thermostat setting above room temperature.
PROCEDURE 5—ADJUSTMENTS
A. Set Gas Input Rate
Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft.
In the U.S.A., the input ratings for altitudes above 2000 ft must be reduced by 2 percent for each 1000 ft above sea level.
In Canada, the input ratings must be derated by 5 percent for altitudes of 2000 ft to 4500 ft above sea level.
Furnace input rate must be within ±2 percent of input on furnace rating plate adjusted for altitude.
1. Determine natural gas orifice size and manifold pressure for correct input.
a. Obtain average gas heat value (at installed altitude) from local gas supplier.
b. Obtain average gas specific gravity from local gas supplier.
c. Verify furnace model and size. Table 13 can only be used for model PG9MAB furnaces with heating sizes of 040 through 120. Table
14 can only be used for model PG9MAB furnaces with heating size of 140.
d. Find installation altitude in Table 13 or 14.
NOTE: For Canada altitudes of 2001 to 4500 ft, use U.S.A. altitudes of 2001 to 3000 ft in Table 13 or 14.
e. Find closest natural gas heat value and specific gravity in Table 13 or 14.
f. Follow heat value and specific gravity lines to point of intersection to find orifice size and manifold pressure settings for proper operation.
EXAMPLE: (0—2000 ft altitude using Table 13)
Heating value = 1050 Btu/cu ft
Specific gravity = 0.62
Therefore: Orifice No. 45
Manifold pressure 3.6-in. wc
* Furnace is shipped with No. 45 orifices. In this example all main burner orifices are the correct size and do not need to be
changed to obtain the proper input rate.
Check and verify burner orifice size in furnace. NEVER ASSUME ORIFICE SIZE; ALWAYS CHECK AND VERIFY.
2. Adjust manifold pressure to obtain input rate.
NOTE: Manifold pressure must always be measured with burner enclosure front REMOVED. Gas meter must always be clocked with burner
enclosure front INSTALLED.
a. Remove burner enclosure front.
b. Remove cap that conceals adjustment screw for gas valve regulator. (See Fig. 48.)
c. Jumper R and W thermostat connections on control to start furnace operation.
-24v terminal on control to the TEST/TWIN 3/16-inch quick-connect terminal on control
OM
-24v terminals are jumpered longer than 2 sec, LED will flash rapidly and ignore component test status code
OM
—51—

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents