Carrier 30GTN Service And Troubleshooting Manual page 70

Air-cooled reciprocating with comfortlink controls 50/60 hz controls, start-up, operation, service, and troubleshooting
Table of Contents

Advertisement

DESCRIPTION
1
Control Mode
2
Occupied
3
CCN Chiller
4
Alarm State
5
Active Demand Limit
6
Percent Total Capacity
7
Requested Stage
8
Load/Unload Factor
9
Active Setpoint
10
Control Point
11
Entering Fluid Temp
12
Leaving Fluid Temp
13
Emergency Stop
14
Minutes Left for Start
DESCRIPTION
1
Circuit A Analog Values
2
Percent Total Capacity
3
Percent Available Cap
4
Discharge Pressure
5
Suction Pressure
6
Saturated Condensing Tmp
7
Saturated Suction Temp
8
Compressor Suction Temp
9
Suction Superheat Temp
10
EXV % Open
DESCRIPTION
1
Circuit A Discretes
2
Fan A1 Relay
3
Fan A2 Relay
4
Oil Pressure Switch
5
Compressor A1 Relay
6
Compressor A2 Relay
7
Compressor A3 Relay
8
Compressor A4 Relay
9
Unloader A1 Relay
10
Unloader A2 Relay
11
Hot Gas Bypass Relay
GENUNIT (General Unit Parameters)
STATUS
0 = Service Test
1 = OFF - local control
2 = OFF-CCN control
3 = OFF-timeclock
4 = Emergency stop
5 = ON-local control
6 = ON-CCN control
7 = ON-timeclock
Yes/No
Start/Stop
Normal
0-100
0-100
nn
snnn.n
snnn.n
snnn.n
snnn.n
snnn.n
Enable/Emstop
nn
CIRCA AN (Circuit A Analog values)
STATUS
0-100
0-100
nnn.n
nnn.n
snnn.n
snnn.n
snnn.n
snnn.n
0-100.0
CIRCA DO (Circuit A Discrete Parameters)
STATUS
ON/OFF
ON/OFF
OPEN/CLOSE
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
70
UNITS
POINT
MODE
OCC
CHIL S S
ALM
%
DEM LIM
%
CAP T
STAGE
SMZ
°F
SP
°F
CTRL PNT
°F
EWT
°F
LWT
EMSTOP
min
MIN LEFT
UNITS
POINT
%
CAPA T
%
CAPA A
PSI
DP A
PSI
SP A
°F
TMP SCTA
°F
TMP SSTA
°F
CTA TMP
^F
SH A
%
EXV A
UNITS
POINT
FAN A1
FAN A2
OILSW A
K A1 RLY
K A2 RLY
K A3 RLY
K A4 RLY
UNL A1
UNL A2
HGAS
FORCEABLE
N
N
Y
N
Y
N
N
N
N
Y
N
N
Y
N
FORCEABLE
N
N
N
N
N
N
N
N
N
FORCEABLE
N
N
N
N
N
N
N
N
N
N