Carrier 30GTN Service And Troubleshooting Manual page 51

Air-cooled reciprocating with comfortlink controls 50/60 hz controls, start-up, operation, service, and troubleshooting
Table of Contents

Advertisement

ALARM/
ALARM OR
ALEERT
DESCRIPTION
ALERT
CODE
203
Alert
Loss of Communica-
tion with Slave Chiller
204
Alert
Loss of Communica-
tion with Master Chiller
206
Alert
High Leaving Chilled
Water Temperature
207
Alarm
Cooler Freeze Protec-
tion
208
Alarm
Low Cooler Fluid Flow
950
Alert
Loss of Communica-
tion with WSM
951
Alert
Loss of Communica-
tion with FSM
LEGEND
CCN
— Carrier Comfort Network
CPCS — Compressor Protection Control System
CXB
— Compressor Expansion Board
EMM
— Energy Management Module
EXV
— Electronic Expansion Valve
FSM
— Flotronic™ System Manager
MBB
— Main Base Board
MOP
— Maximum Operating Pressure
WSM
— Water System Manager
Table 27 — Alarm and Alert Codes (cont)
WHY WAS THIS
ALARm
GENERATED?
Master MBB loses
communication with
Slave MBB
Slave MBB loses com-
munication with Master
MBB
LWT read is greater
than LCW Alert Limit,
Total capacity is 100%
and LWT is greater
than LWT reading one
minute ago
Cooler EWT or LWT is
less than freeze*
Cooler EWT is less
than LWT by 3° F
(1.7° C) for 1 minute
after a circuit is started
No communications
have been received by
MBB within 5 minutes
of last transmission
No communications
have been received by
MBB within 5 minutes
of last transmission
51
ACTION TAKEN
BY CONTROL
METHOD
Dual chiller control dis-
Automatic
abled. Chiller runs as a
stand-alone machine.
Dual chiller control dis-
Automatic
abled. Chiller runs as a
stand-alone machine
Alert only. No action
Automatic
taken.
Chiller shutdown with-
Automatic for first
out going through
occurrence of day.
pumpdown. Cooler
Manual reset
pump continues to run
thereafter.
(if control enabled).
Chiller shutdown with-
out going through
pumpdown. Cooler
pump shut off (if con-
trol enabled).
WSM forces removed.
Automatic
Chiller runs under own
control.
FSM forces removed.
Automatic
Chiller runs under own
control.
*Freeze is defined as 34° F (1.1 C) for water. For brine fluids, freeze
is CSP.1 −8° F (4.4 C) for single set point and lower of CSP.1/CSP.2
−8° F (4.4 C) for dual set point configuration.
NOTE: The following table shows illegal configurations:
1 Zero compressors in a circuit
2 Four compressors in a circuit with two unloaders
Four compressors in a circuit with one unloader and hot gas
3
bypass
4 Two unloaders and hot gas bypass in a circuit.
5 More than one compressor quantity difference between circuits
6 Fluid type of low temperature brine
7 Air cooled head pressure control with common fan staging and
different head pressure control methods for each circuit.
RESET
PROBABLE
CAUSE
Wiring error, faulty wir-
ing, failed Slave MBB
module, power loss at
Slave chiller, wrong
slave address.
Wiring error, faulty wir-
ing, failed Master MBB
module, power loss at
Master chiller.
Building load greater
than unit capacity, low
water/brine flow or
compressor fault.
Check for other
alarms/alerts.
Faulty thermistor (T1/
T2), low water flow.
Manual
Faulty cooler pump,
low water flow, plugged
fluid strainer.
Failed module, wiring
error, failed trans-
former, loose connec-
tion plug, wrong
address.
Failed module, wiring
error, failed trans-
former, loose connec-
tion plug, wrong
address.