Carrier 30GTN Service And Troubleshooting Manual page 50

Air-cooled reciprocating with comfortlink controls 50/60 hz controls, start-up, operation, service, and troubleshooting
Table of Contents

Advertisement

ALARM/
ALARM
ALEERT
OR
DESCRIPTION
CODE
ALERT
150
Alarm
Emergency Stop
151
Alarm
Illegal Configuration
152
Alarm
Unit Down Due to
Failure
153
Alarm
Real Time Clock Hard-
ware Failure
154
Alarm
Serial EEPROM Hard-
ware Failure
155
Alert
Serial EEPROM Stor-
age Failure
156
Alarm
Critical Serial
EEPROM Storage
Failure
157
Alarm
A/D Hardware Failure
170
Alert
Loss of Communica-
tion with CXB
172
Alarm
Loss of Communica-
tion with EXV
173
Alert
Loss of Communica-
tion with EMM
174
Alert
4 to 20 mA Cooling Set
Point Input Failure
176
Alert
4 to 20 mA Tempera-
ture Reset Input Fail-
ure
177
Alert
4 to 20 mA Demand
Limit Input Failure
200
Alarm
Cooler Pump Interlock
Failure to Close at
Start-Up
201
Alarm
Cooler Pump Interlock
Opened During Normal
Operation
202
Alarm
Cooler Pump Interlock
Closed When Pump is
Off
Table 27 — Alarm and Alert Codes (cont)
WHY WAS THIS
ACTION TAKEN
ALARm
GENERATED?
CCN emergency stop
Chiller shutdown with-
command received
out going through
pumpdown.
One or more of the
Chiller is not allowed to
illegal configurations
start.
shown in the Note be-
low exists.
Both circuits are down
Chiller is unable to run. Automatic once
due to alarms/alerts.
Internal clock on MBB
Occupancy schedule
fails
will not be used. Chiller
defaults to Local On
mode.
Hardware failure with
Chiller is unable to run.
MBB
Configuration/storage
No Action
failure with MBB
Configuration/storage
Chiller is not allowed to
failure with MBB
run.
Hardware failure with
Chiller is not allowed to
peripheral device
run.
MBB loses communi-
Compressors A3, A4
cation with CXB
and B3 and unloaders
A2/B2 unable to
operate.
MBB loses communi-
Chiller shutdown with-
cation with EXV
out going through
pumpdown.
MBB loses communi-
4 to 20 mA tempera-
cation with EMM
ture reset disabled.
Demand Limit set to
100%. 4 to 20 mA set
point disabled.
If configured with EMM
Set point function dis-
and input less than
abled. Chiller controls
2 mA or greater than
to CSP1.
22 mA
If configured with EMM
Reset function dis-
and input less than
abled. Chiller returns
2 mA or greater than
to normal set point
22 mA
control.
If configured with EMM
Demand limit function
and input less than
disabled. Chiller re-
2 mA or greater than
turns to 100% demand
22 mA
limit control.
If configured for cooler
Cooler pump shut off.
pump control and
Chiller shutdown with-
cooler pump interlock
out going through
not closed within
pumpdown.
1 minute after pump is
started
If configured for cooler
Cooler pump shut off.
pump control and inter-
Chiller shutdown with-
lock opens while cooler
out going through
pump relay is on
pumpdown.
If configured for cooler
Chiller is not allowed to
pump control and inter-
start.
lock closes while
cooler pump relay
is off
50
RESET
BY CONTROL
METHOD
Automatic once CCN
command for EMSTOP
returns to
normal
Manual once configu-
ration errors are
corrected
alarms/alerts are
cleared that prevent
the chiller from
starting.
Automatic when cor-
rect clock control
restarts.
Manual
Manual
Manual
Manual
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Manual
Manual
Manual
PROBABLE
CAUSE
CCN Network
command.
Configuration error.
See Note on
page 49.
Alarm notifies user
that chiller is
100% down.
Main Base Board
failure.
Main Base Board
failure.
Potential failure of
MBB. Download cur-
rent operating soft-
ware. Replace MBB
if error occurs
again.
Main Base Board
failure.
Main Base Board
failure.
Wiring error, faulty
wiring or failed CXB
module.
Wiring error, faulty
wiring or failed EXV
module.
Wiring error, faulty
wiring or failed
Energy Manage-
ment Module (EMM).
Faulty signal generator,
wiring error, or faulty
EMM.
Faulty signal generator,
wiring error, or faulty
EMM.
Faulty signal generator,
wiring error, or faulty
EMM.
Failure of cooler pump
or controls.
Failure of cooler pump
or controls.
Failure of cooler pump
relay or interlock,
welded contacts.