B. Through The Wall
Horizontal termination cap must be a minimum of 12 inches.
(305mm) from the wall. Approved for mobile home instal-
lations. Must use 3 or 4 inch (76-102mm) "L" or "PL" listed
pellet venting or listed double wall pipe and a Quadra-Fire
Outside Air Kit in mobile homes.
Straight Out
NOTICE:
Please note that while the minimum
clearance for the termination cap is 6
inches (152mm) there is the possibly
of soot buildup around the termina-
tion area. If this occurs we suggest
to move the termination further away
from the house to prevent it.
45 Degree
Page 14
NOTE:
In Canada, where passage through a wall or partition of
combustible construction is desired, the installation shall
conform to CAN/CSA-B365
6 in.
(152mm)
Minimum
From Glass
Figure 14.1
Illustration shows venting going in both directions.
Choose which one is best for your installation.
Wall
Thimble
6 in.
(152mm)
Minimum
2 in.
(51mm)
Minimum
Figure 14.2
7050-128B
Santa Fe Pellet Stove
2 in.
(51mm)
Minimum
Wall
Thimble
6 in.
(152mm)
Minimum
Non-combustible Hearth Pad
6 in. (152mm)
Minimum
2 in. (51mm)
Minimum
Horizontal
Termination
Cap
September 3, 2009