Venting - Empire Comfort Systems BVD34FP Installation Instructions And Owner's Manual

The keystone "b" vent zero clearance gas fireplace
Table of Contents

Advertisement

Vent size
Model BVD34FP series uses a 4" B-Vent for operation.
Models BVD36FP and BVP42FP series use a 6" B-Vent for
operation.
never downsize venting diameters.
Clearances
Vent clearances are per vent manufacturer's specifications
Vent Configuration
Various venting configurations are shown in Figures 14 and 15
from which maximum vent runs can be determined.
wArnInG - rIsK of fIre!
Always maintain minimum clearances or greater around
the vent system. Do not pack air spaces with insulation or
other material.
40 ft. Max.
11 ft. Min.
Vertical Venting - no elbows
22679-1-0408
VENTING (CONT)
Minimum clearances are
per vent manufacturer's
specifications
Vent supports are per
vent manufacturer's
specifications
figure 14
offset Venting - with elbows
Maximum horizontal
distance is 50% of
vertical vent height
11 ft. Min.
90 - degree or
45 - degree Elbows
Straight Section
Figure 15
5 ft. Max.
Horizontal at
11 ft.
Min.
Vent supports per
Vertical
manufacturers vent
specifications
Horizontal vent
to maintain a 1/4"
rise per ft. Min.
2 ft. Minimum off top of
unit before using elbows
Page 13