Cutting A Hole And Mounting Installation Plate - Toshiba Carrier RAV-SP180KRT-UL Installation Manual

Indoor unit high-wall type
Table of Contents

Advertisement

Available languages

Available languages

+001111052201_00Ta.book Page 8 Friday, November 20, 2009 11:45 AM
High-Wall Type
5
CUTTING A HOLE AND MOUNTING INSTALLATION
PLATE
Cutting a hole
In case of installing the refrigerant pipes from the
rear:
1. Decide the hole position for piping at 7.1"
(180 mm) from the arrow mark ( ) on the
installation plate and drill a hole at a slight
downward slant toward outdoor side.
Pipe hole; dia.2.6" (65 mm): SP180 type
Pipe hole; dia.3.1" (80 mm): SP240 type
80
65
1111012101
The centre of the pipe hole is above the arrow
7.1" (180 mm)
NOTE
• When drilling a wall that contains a metal lath,
wire lath or metal plate, be sure to use a pipe
hole brim ring sold separately.
80
65
1111012101
0.9" (23 mm)
Pipe hole
dia. 2.6" (65 mm):
SP180 type
dia. 3.1" (80 mm):
SP240 type
– 8 –
Mounting the installation plate
Be sure that the installation plate is fix to the wall
with screws to make the indoor unit fit to the wall.
Anchor bolt holes
Hook
Hook
Pipe hole
Mounting
Thread
Screw
Indoor unit
Weight
When the installation plate is
directly mounted on the wall
1. Securely fit the installation plate onto the
wall by screwing it in the upper and lower
parts to hook up the indoor unit.
2. To mount the installation plate on a
concrete wall with anchor bolts, utilize the
anchor bolt holes as illustrated in the above
figure.
3. Install the installation plate horizontally in
the wall.
CAUTION
When installing the installation plate with a
mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
Installation Manual
0.9 " (23 mm )
Hook
Pipe hole
(dia. 2.6" (65 mm))
dia. 3.1" (80 mm))
Installation plate
EN
8-EN
Toshiba