Performance data (cont)
EWT (F)
GPM
7.5
60
11.3
15.0
7.5
70*
11.3
15.0
7.5
80
11.3
15.0
7.5
85*
11.3
15.0
7.5
90
11.3
15.0
7.5
95
11.3
15.0
LEGEND
EWT — Entering Water Temperature (F)
GPM — Gallons Per Minute
TC
— Total Capacity (MBtuh)
THA — Total Heat of Absorption (MBtuh)
THR — Total Heat of Rejection (MBtuh)
TSC — Total Sensible Capacity (MBtuh)
24
50RHC,RVC060 — 2000 CFM NOMINAL AIRFLOW
PRESSURE DROP
PSI
Ft Wg
TC
4.4
10.1
60.5
7.6
17.5
61.2
11.5
26.7
61.6
4.2
9.7
59.0
7.3
16.9
60.1
11.1
25.6
60.5
4.1
9.4
56.8
7.1
16.4
58.3
10.8
25.0
59.0
4.0
9.3
55.4
7.0
16.2
57.2
10.7
24.6
57.9
4.0
9.2
53.9
6.9
16.0
55.8
10.5
24.3
56.7
3.9
9.1
52.1
6.8
15.8
54.3
10.4
24.0
55.3
COOLING
TSC
kW
THR
43.1
4.36
75.4
43.2
4.17
75.5
43.3
4.08
75.5
42.9
4.68
74.9
43.1
4.46
75.3
43.2
4.36
75.4
42.4
5.04
74.0
42.8
4.80
74.7
42.9
4.68
74.9
42.0
5.23
73.3
42.5
4.98
74.1
42.7
4.86
74.5
41.4
5.44
72.4
42.1
5.17
73.5
42.4
5.04
73.9
40.5
5.66
71.4
41.6
5.38
72.7
42.0
5.24
73.2
NOTES:
1. Interpolation is permissible, extrapolation is not.
2. All entering air conditions are 80 F db (dry bulb) and 67 F wb (wet
bulb) in cooling and 70 F db in heating.
3. All performance data is based upon the lower voltage of dual voltage
rated units.
4. See Performance Correction tables for operating conditions other
than those listed above.
5. Data table does not reflect ISO pump or fan corrections.
6. Performance capacities shown in thousands of Btuh.
HEATING
TC
kW
THA
63.0
5.02
45.9
67.4
5.17
49.8
69.8
5.25
51.9
72.6
5.34
54.4
77.0
5.49
58.2
79.2
5.56
60.2
80.6
5.61
61.5
84.4
5.74
64.8
86.2
5.80
66.4
83.9
5.73
64.4
87.3
5.84
67.4
88.7
5.89
68.7
86.8
5.82
66.9
89.5
5.91
69.4
90.6
5.95
70.3
Operation Not Recommended