Carrier AQUAZONE 50RHC006-060 Series Product Data page 13

Standard efficiency water source heat pumps, horizontal — 1/2 to 5 nominal tons, vertical — 3/4 to 5 nominal tons
Table of Contents

Advertisement

VII ARI/ISO/ASHRAE 13256-1 Conversion
Performance standard ARI/ISO/ASHRAE 13256-1
became effective on January 1, 2000 and replaced
the existing ARI Standards 320 Water-Loop Heat
Pumps (WLHP), 325 Ground-Water Heat Pumps
(GWHP), and 330 Ground-Loop Heat Pumps
(GLHP).
The ARI/ISO Standard incorporates a consistent
rating methodology for including fan and pump
energy for calculating cooling capacity, heating
capacity, and energy efficiency ratios (EER). This
simplifies the use of rating data for heat pump per-
formance modeling in seasonal energy analysis cal-
culations, and allows for direct rating comparisons
across applications.
a) ISO Capacity and Efficiency Equations
The following equations are used to calculate and
correct cooling capacity, heating capacity, and
respective EER:
ISO Cooling Capacity = (Cooling Capacity in
Btuh) + (Fan Power Correction in Watts x 3.412)
ISO Cooling EER = (ISO Cooling Capacity in
Btuh/3.412)/(Power Input in watts – fan power
correction in watts + pump power correction in
watts) = Watts/Watts
NOTE: Do not divide ISO Cooling Capacity by
3.412 to obtain Btuh/Watts.
ISO Heating Capacity = (Heating Capacity in
Btuh) – (Fan Power Correction in Watts x 3.412)
ISO Heating EER = (ISO Heating Capacity in
Btuh/3.412)/(Power Input in watts – fan power
correction in watts + pump power correction in
watts) = Watts/Watts
NOTE: Do not divide ISO Heating Capacity by
3.412 to obtain Btuh/Watts.
Refer to English to SI conversion table in this
book.
b) Identify the design conditions corrected for air and
water conditions.
Airflow Cfm = 700 cfm
Water Flow
(Based upon 12 F rise in temp) = 4.5 gpm
External Static Pressure = 0.4 in. wg
Water Pressure Drop = 8.1 ft of head
Power input = 2,010 watts
Cooling Capacity = 22,360 Btuh
c) Perform Fan Power Correction Adjustment
Use the following formula to calculate Fan Power
Correction:
Fan Power
Correction = (Cfm x 0.472) x (External Static
Pressure x 249)/300 = Watts
= (700 x 0.472) x (0.4 x 249)/300
= 110 Watts
d) Perform Pump Power Correction Adjustment
Use the following formula to calculate Pump
Power Correction:
Pump Power
Correction
= (Gpm x 0.0631) x (Pressure Drop
x 2,990)/300
= Watts
= (4.5 x 0.0631) x
(8.1 x 2,990)/300
= 23 Watts
e) Perform capacity and EER calculations
Use the following formula to calculate capacity
and EER:
ISO Cooling
Capacity
= (Cooling Capacity) + (Fan Power
Correction x 3.412)
= 22,360 + (110 x 3.412)
= 22,735 Btuh
f) Perform Corrections by using the ISO Equations
ISO EER = (ISO Cooling Capacity/3.412)/
(Power Input – Fan Power Correc-
tion + Pump Power Correction)
= Watts/Watts
NOTE: Do not divide ISO Cooling Capacity by
3.412 to obtain Btuh/Watts.
= (22,735/3.412)/(2,010 – 110 + 23)
= 3.47 Watts/Watt
= 11.82 Btuh/Watt
13