Part 2 Functions & Controls

4.2 How to Set E.S.P?

This Function can be controled with new wired remote controller
Procedure of RPM change:
Ex) External static pressure is 29Pa for model name "AMNW12GB1A0[LMDN125HV]".
• To protect the unit, compressor is designed to be off during E.S.P. setting.
• E.S.P function is setting the volume of each fan speed.
It is for the convenience of installation.
It is recommended that you should not use this function while using the remote controller.
PQRCUCS0C
Defrost
Preheat
TEMP
FAN
MODE
SPEED
TEMP
Copyright ©2010 LG Electronics. Inc. All right reserved.
Only for training and service purposes
1
2
Out door
Room Temp
Total on
Central Run
3
4
❈ The E.S.P value is set at the proper value at the factory.
Press the mode button and the temperature increasing
button(▲) same time for three seconds.
Set the volume of each fan speed(Low, Medium, Hi)
by using the temperature control button. Press the fan
speed button to select the fan speed.
The value of E.S.P can be adjusted from 1 to 255.
If you press the On/Off button while setting the ESP
function, it will be canceled. (The picture on the left
side is the example of setting the Hi wind to ESP 09.)
Press the mode button and the temperature increasing
button (s) same time for three seconds. Then the ESP
setting will be activated after the temperature display
flashes three times.
Lo
Setting the Low wind to 210
So it is highly recommended that you should not change
the E.S.P value at your discretion.
- 16 -
Med
100
Setting the Medium wind to 175