E.S.P. setting value (reference)
Static pressure(mmAq)
Model name
Step(Hi/Mid/Lo)
8.5 CMM(300CFM)
AMNW09GB1A0
7.5 CMM(265CFM)
[LMDN095HV]
6.5 CMM(230CFM)
9.5 CMM(335CFM)
AMNW12GB1A0
8.5 CMM(300CFM)
[LMDN125HV]
7.5 CMM(265CFM)
15 CMM(530CFM)
AMNW18GB2A0
13.5 CMM(477CFM)
[LMDN185HV]
11.5 CMM(406CFM)
[ Notes ]
1. To get the desired Airflow & E.S.P. combination from the table set the matching value from the table. Value other than
that in table will not give the combinations of airflow & E.S.P. which are mentioned in the table.
2. Table data is based at 230V. According to the fluctuation of voltage, air flow rate varies.

4.3 High Ceiling operation

Function to Control the Air Volume by Ceiling Height Control of the air intensity has been made possible by employing a
height-control algorithm for the interior fan.
According to the height of the installation, it provides variability of indoor fan motor rpm. If the height of installation is low
then you can adjust low rpm of indoor fan motor. On the other hand if the height of the installation is high you can adjust
high rpm of indoor fan motor. Selection of speed can be done by slide switch at the back of the LCD wired remote.
Copyright ©2010 LG Electronics. Inc. All right reserved.
Only for training and service purposes
0
75
69
62
82
75
69
90
82
75
Installation on the
normal-height ceiling
1
2
Setting value
84
94
77
88
71
83
90
99
84
94
77
88
97
105
90
99
84
93
installation on the
higher ceiling
- 17 -
Part 2 Functions & Controls
3
4
104
114
99
110
95
106
109
118
104
114
99
110
114
122
109
119
103
114
LGE Internal Use Only