Table Inspection Of Outdoor Unit Main Parts - Toshiba RAV-SP454ATP-E Service Manual

Split type outdoor unit
Hide thumbs Also See for RAV-SP454ATP-E:
Table of Contents

Advertisement

8-3. Table Inspection of outdoor unit main parts

No.
Parts name
1
Compressor
(Model : DA150A1F-20F)
2
Compressor
(Model : DA150A1F-21F)
3
Compressor
(Model : DA220A2F-22L)
4
Fan motor
(Model : ICF-140-43-4R)
5
Fan motor
(Model : ICF-280-A60-1)
SVM-12085_051-114.indd 74
SVM-12085_051-114.indd 74
Checking procedure
Measure the resistance value of each winding by using the tester.
Red
White
Black
Measure the resistance value of each winding by using the tester.
Red
White
Black
Measure the resistance value of each winding by using the tester.
Red
White
Black
Measure the resistance value of each winding by using the tester.
Red
White
Black
Measure the resistance value of each winding by using the tester.
Red
White
Black
– 74 –
FILE NO. SVM-12085
Position
Resistance value
Red – White
0.93 Ω
White – Black
Black – Red
Under 20°C
Position
Resistance value
Red – White
1.07 Ω
White – Black
Black – Red
Under 20°C
Position
Resistance value
Red – White
0.606 Ω
White – Black
Black – Red
Under 20°C
Position
Resistance value
Red – White
21.00±1.05 Ω
White – Black
Black – Red
Under 20°C
Position
Resistance value
Red – White
32.6±3.3 Ω
White – Black
Black – Red
Under 20°C
12/06/12 11:15 AM
12/06/12 11:15 AM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents