RAV-SP40
ATP
No.
1
Compressor
2
Fan motor
3
4-way valve coil
4
PMV coil
5
P.C. board
6
Reactor
7
Fuse (Switching power (Protect))
8
Fuse (Inverter, input (Current protect))
9
Outdoor temp. sensor (To sensor)
10
Heat exchanger sensor (Te sensor)
11
Suction temp. sensor (Ts sensor)
12
Discharge temp. sensor (Td sensor)
13
Compressor thermo. (Protection)
RAV-SP80
*
ATP
*
No.
1
Compressor
2
Fan motor
3
4-way valve coil
4
PMV coil
5
P.C. board
6
Reactor
7
Fuse (Mounted on P.C. board)
8
Fuse (Mounted on P.C. board)
9
Fuse (Mounted on P.C. board)
10
Outdoor temp. sensor (To sensor)
11
Heat exchanger sensor (Te sensor)
12
Suction temp. sensor (Ts sensor)
13
Discharge temp. sensor (Td sensor)
14
Heat exchanger temp. sensor (Tl sensor)
15
Compressor thermo. (Protection)
SVM-12085_001-050.indd 26
SVM-12085_001-050.indd 26

5. SPECIFICATIONS OF ELECTRICAL PARTS

*
*
*
, SP45
ATP
, SP56
ATP
Parts name
Parts name
*
Type
40, 45 : DA150A1F-20F
56 : DA150A1F-21F
ICF-140-43-4R
STF-H01AJ1872A1
CAM-MD12TCTH-5
MCC-5009
CH-57
-
-
-
-
-
-
CS-12AL
Type
DA220A2F-22L
ICF-280-A60-1
STF-H01AP1874A
CAM-MD12TCTH-6
MCC-1571
CH-56
-
-
-
-
-
-
-
-
CS-12AL
– 26 –
FILE NO. SVM-12085
Specifications
3 phase, 4P, 1100 W
Output 43 W
-
-
-
10mH, 16A
T3.15A, AC 250V
AC240V
10 kΩ at 25°C
10 kΩ at 25°C
10 kΩ at 25°C
50 kΩ at 25°C
OFF: 125 ± 4°C, ON: 90 ± 5°C
Specifications
Output 60 W
-
-
-
5.8 mH, 18.5 A
AC250 V, 25 A
AC250 V, 10 A
AC250 V, 3.15 A
10 kΩ at 25°C
10 kΩ at 25°C
10 kΩ at 25°C
50 kΩ at 25°C
50 kΩ at 25°C
OFF: 125 ± 4°C, ON: 90 ± 5°C