Toshiba RAV-SP454ATP-E Service Manual page 23

Split type outdoor unit
Hide thumbs Also See for RAV-SP454ATP-E:
Table of Contents

Advertisement

RAV-SP80 ATP
TS sensor
TD
sensor
Accumulator
Sub-ass'y
Accumulator
(1.8L)
Rotary compressor
(DA220A2F-22L)
In cooling operation
In heating operation
Pd
Standard
2.79
Cooling
Overload
3.53
Low load
1.71
Standard
2.65
Heating
Overload
3.20
Low load
2.33
SVM-12085_001-050.indd 23
SVM-12085_001-050.indd 23
TO sensor
4-way valve
(STF-0218G)
Muffler
Muffler
Ø8, 2 rows, 34 stages
Ø25 × L180
Ø25 × L210
Pressure
Pipe surface temperature (°C)
(MPa)
(kg/cm²g)
Discharge
Ps
Pd
Ps
(TD)
0.89
27.3
8.7
70
1.07
34.6
10.5
81
0.72
16.8
7.1
42
0.68
26.0
6.7
74
1.11
31.4
10.9
76
0.21
22.8
2.1
93
TL sensor
Ø2 × Ø3 × 600L
Ø2 × Ø3 × 550L
Ø2 × Ø3 × 450L
TE sensor
Ø2 × Ø3
× 450L
Capillary
Heat exchanger
FP1.45, flat fin
Strainer
Indoor heat
Outdoor heat
Suction
exchanger
exchanger
(TS)
(TC)
(TE)
13
11
39
17
14
48
7
3
18
4
44
3
19
52
15
–18
31
–20
– 23 –
FILE NO. SVM-12085
PMV
(Pulse Motor Valve)
(CAM-B30YGTF-2)
Strainer
Refrigerant pipe
at liquid side Ø9.5
Packed valve
Refrigerant pipe
at gas side Ø15.9
Ball valve
R410A 2.1 kg
Indoor/Outdoor
Compressor
temp. conditions
drive revolution
Indoor
(DB/WB) (°C)
frequency
fan
(rps)
Indoor
Outdoor
58.2
HIGH
27 / 19
65.0
HIGH
32 / 24
30.0
LOW
18 / 15.5
61.5
HIGH
20 / –
28.0
LOW
30 / –
99.6
HIGH
15 / –
35 / –
43 / –
–15 / –
7 / 6
24 / 18
–20 / –
12/06/12 11:06 AM
12/06/12 11:06 AM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents