Auto-Stop In Case Of Lower-Limit Frequency Continuous Operation - Toshiba TOSVERT VF-FS1 Instruction Manual

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-FS1:
Table of Contents

Advertisement

6.8
Auto-stop in case of lower-limit frequency continuous
operation
6.8.1
 : Auto-stop in case of lower-limit frequency continuous operation
 : Hysteresis for LL stop operation
 : Restart deviation for LL stop operation
 : Restart feedback for LL stop operation
• Function
If operation is carried out continuously at a frequency command below the lower-limit frequency (  ) for
the period of time set with  , the inverter will automatically slow down the motor to a stop. At that
6
time, "  " is displayed (alternately) on the operation panel.
This function will be canceled if a frequency command above the lower-limit frequency (  )
+  Hz.
PID control selected-> The stop of this function will be canceled by deviation and feedback when
f392 and f393 is setting.
[Parameter setting]

f391
f392
f393
Auto-stop in case of lower-limit frequency continuous
operation
Title
Function
Auto-stop in case of lower-limit
frequency continuous operation time
Hysteresis for LL stop operation
Restart deviation for LL stop operation
Restart feedback for LL stop operation
Adjustment range
0.0: Disabled
0.1-600.0 (s)
0.0- fh
0.0- fh
0.0- fh
F-26
E6581381
Default setting
0.0
0.2
0.0
0.0