3.0 PRE-INSTALLATION PREPARATION

3.1

APPLIANCE PLACEMENT

Have an authorized dealer install the appliance. If you install the appliance yourself, have your dealer review
your installation plans and/or installation.
Draw out a detailed plan of the installation including dimensions and verify the dimensions with the require-
ments listed in this manual.
You may wish to adjust the appliance position slightly to ensure the vent does not intersect with a framing
member. Appliance must be positioned so that no combustibles are within, or can swing within (e.g. drapes,
doors), 48" of the front of the appliance.
3.2

CLEARANCE TO COMBUSTIBLES

DO NOT INSTALL INTO ANY AREA HAVING A HEIGHT LESS THAN 7 FEET (CEILING OF ENCLOSURE
PARALLEL & CORNER
SIDEWALL (A)
SIDEWALL TO FLUE (B)
BACKWALL (C)
BACKWALL TO FLUE (D)
CORNER (E)
CEILING (F)
Clearances can be reduced with shielding acceptable to local authorities. Reduced installation must comply
with NFPA 211 or CAN/CSA-B365.
3.3

ALCOVE INSTALLATION

1100 series only may be installed, using a listed double wall connector,
such as Security DL6 in Canada, the Simpson Duravent Plus DVL in
the USA or an equivalent double wall connector, into an alcove having
a depth of no more than 4 feet and a height of at least 7 feet.
The minimum clearances are as shown.
TO APPLIANCE BOTTOM, EXCLUDING HEARTH HEIGHT).
BACK WALL
D
C
A
B
SINGLE WALL CONNECTOR
1100PL / 1100C
12"
21 3/4"
10"
13 1/2"
6"
84"
WARNING
!
BACK WALL
E
E
1400PL / 1400C
1100PL / 1100C
12"
21 3/4"
12"
16 1/2"
6"
84"
67.1A
F
DOUBLE WALL CONNECTOR
1400PL / 1400C
10"
10"
19 3/4"
19 3/4"
6"
6"
9 1/2"
10 1/2"
2"
4"
84"
84"
9"
6"
14"
23"
ALCOVE
W415-0762 / A / 07.19.10
9
4 FOOT
MAX