HORIZONTAL INSTALLATION
EXHAUST VENT TERMINATION SHALL BE AS FOLLOWS:
A MINIMUM OF 4 FEET/122Omm BELOW, BESIDE AND 1 FOOT ABOVE ANY DOOR
OR WINDOW THAT OPENS, OR ANY OPENING INTO A BUILDING.
A MINIMUM OF 2 FEET/610mm FROM ANY ADJACENT BUILDING OR OVERHANG.
A MINIMUM OF 7 FEET/2130mm ABOVE GRADE, WHEN LOCATED ADJACENT TO
PUBLIC WALKWAYS.
A MINIMUM OF 2 FEET/610mm ABOVE GRASS, PLANTS OR OTHER COMBUSTIBLES.
Note: The pipe lengths shown are for reference only.
Your actual pipe length requirements may differ.
SINGLE WALL PIPE SHALL NOT BE
USED FOR ANY INSTALLATION.
HORIZONTAL INSTALLATION SHALL
BE A MAXIMUM OF 5' FEET.
WARNING:
Vent surfaces can become hot enough to cause burns
if touched. Non-combustible shielding may be required.
PLEASE FOLLOW THE PIPE MANUFACTURER'S INSTRUCTIONS AND LOCAL
BUILDING CODES FOR THE CLEARANCES TO COMBUSIBLES REQUIRED FOR
INSTALLATION OF THE VENT PIPE BEING USED.
(9)