Condensate Disposal; Condensate Disposal Condensate Drain - Lochinvar 151 - 801 Operation Manual

Armor outdoor armor water heater
Hide thumbs Also See for 151 - 801:
Table of Contents

Advertisement

6

Condensate disposal

Condensate drain
1. This water heater is a high efficiency appliance that
produces condensate.
2. The side of the water heater has a 1/2 inch PVC union
for connection of a 1/2 inch PVC pipe (FIG. 6-1).
3. Slope condensate tubing down and away from the water
heater into a drain or condensate neutralizing filter.
Condensate from the outdoor water heater will be
slightly acidic (typically with a pH from 3 to 5). Install
a neutralizing filter if required by local codes.
A Neutralizer Kit (FIG. 6-1) is available from the factory
(KIT3087 for Models 151 - 501 and KIT3046 for Models
601 - 801).
4. Install the 1/2 inch PVC tee assembly (shipped with the
unit) as shown in FIG. 6-1.
5. Leave the top of the 1/2 inch tee OPEN. This is needed
as a vacuum break.
6. Do not expose condensate line to freezing temperatures.
Precautions should be taken to protect the condensate
management and disposal system during extended
periods of outdoor temperatures below 32°F.
7. Use only plastic tubing or piping as a condensate drain
line (FIG. 6-1).
Figure 6-1 Condensate Disposal
1/2" PVC TEE ASSEMBLY
(FACTORY SUPPLIED)
FLOOR DRAIN OR
DRAIN PAN
Outdoor Armor Water Heater
NOTICE
NOTICE
8. A condensate removal pump is required if the water heater
is below the drain. When installing a condensate pump,
select one approved for use with condensing water heaters
and furnaces. The pump should have an overflow switch
to prevent property damage from condensate spillage. The
switch should be wired in series with the blocked drain
switch inside the water heater (see FIG. 7-1 on page 30).
NEUTRALIZER KIT
KIT3087 shown for illustration purposes.
Installation & Operation Manual
Use materials approved by the authority
having jurisdiction. In the absence of other
authority, PVC and CPVC pipe must comply
with ASTM D1785 or D2845. Cement and
primer must comply with ASME D2564 or
F493.
To allow for proper drainage on large
horizontal runs, a second line vent may
be required and tubing size may need to
increase to 1 inch.
The
condensate
unobstructed, allowing free f low of
condensate.
If condensate is allowed to
freeze in the line or if the line is obstructed
in any other manner, condensate can exit
from the water heater tee, resulting in
potential water damage to property.
IMG00300
1/2" PVC UNION
(FACTORY SUPPLIED)
line
must
remain
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents