Check Inlet Gas Supply - Lochinvar 151 - 801 Operation Manual

Armor outdoor armor water heater
Hide thumbs Also See for 151 - 801:
Table of Contents

Advertisement

4
Gas connections
Table 4A Natural Gas Pipe Size Chart
Nominal
Iron Pipe
Size (Inches)
10
20
1/2
175
120
3/4
369
256
1
697
477
1-1/4
1400
974
1-1/2
2150
1500
2
4100
2820
2-1/2
6460
4460
3
11200
7900
4
23500 16100 13100 11100 10000
Outdoor Armor water heaters are typically shipped ready to fire on natural gas. Check the water heater rating
WARNING
plate to determine which fuel the water heater is set for. If set to natural gas, it may be converted to LP by
installing an orifice or by making a gas valve adjustment (see pages 11 and 12). In order to operate on LP gas,
an orifice MUST BE installed or a gas valve adjustment MUST BE made. Failure to comply could result in severe
personal injury, death, or substantial property damage.

Check inlet gas supply

CSA or UL listed flexible gas connections are
NOTICE
acceptable, but you must exercise caution to
ensure that the line has adequate capacity
to allow your water heater to fire at full
rate. Consult with local codes for proper
installation or service procedures.
DO NOT adjust or attempt to measure
WARNING
gas valve outlet pressure. The gas valve is
factory-set for the correct outlet pressure.
This setting is suitable for natural gas and
propane, requiring no field adjustment.
Attempting to alter or measure the gas valve
outlet pressure could result in damage to
the valve, causing potential severe personal
injury, death, or substantial property damage.
The gas piping must be sized for the proper flow and length of
pipe, to avoid excessive pressure drop. Both the gas meter and
the gas regulator must be properly sized for the total gas load.
If you experience a pressure drop greater than 1 inch w.c., the
meter, regulator, or gas line is undersized or in need of service.
Perform the steps below when checking inlet gas supply:
1.
Turn the main power switch to the "OFF" position.
2.
Shut off gas supply at the manual gas valve in the gas
piping to the appliance.
3.
On Models 151 - 501 loosen the set screw one (1) full
turn from inside the pressure tap on top of the gas valve.
On Models 601 - 801 remove the 1/8" (3 mm) pipe plug
on the inlet flange to the valve and install a suitable 1/8"
(3 mm) fitting (field supplied) for the manometer tubing.
Place the tubing of the manometer over the tap once the
set screw is loosened or the 1/8" (3 mm) fitting is installed
(depending on model) as shown in FIG.'s 4-6 thru 4-9 on
page 24.
4.
Slowly turn on the gas supply at the field installed
manual gas valve.
Outdoor Armor Water Heater
(continued)
Natural Gas Pipe Capacity Chart
Length of Pipe in Straight Feet for 1/2 PSI
30
40
50
60
97
82
N/A
N/A
205
174
155
141
384
328
292
267
789
677
595
543
1210
1020
923
830
2260
1950
1720
1560
3610
3100
2720
2460
6400
5400
4870
4410
9000
Installation & Operation Manual
Single Unit
70
80
90
100
N/A
N/A
N/A
N/A
128
121
113
106
246
236
210
200
502
472
441
410
769
707
666
636
1440
1330
1250
1180
2310
2100
2000
1900
4000
3800
3540
3330
8300
7690
7380
6870
5.
Turn the power switch to the "ON" position.
6.
Adjust the temperature set point on the control panel of
the SMART SYSTEM control module to call for heat.
7.
Observe the gas supply pressure as the burner fires at
100% of rated input. Percent of burner input will be
displayed on the control panel.
8.
Ensure inlet pressure is within specified range.
Minimum and maximum gas supply pressures are
specified in this section of the manual.
9.
If gas supply pressure is within normal range and no
adjustments are needed, proceed on to Step 11.
10. If the gas pressure is out of range, contact the gas utility,
gas supplier, qualified installer or service agency to
determine the necessary steps to provide proper gas
pressure to the control.
11. Turn the power switch to the "OFF" position.
12. Shut off the gas supply at the manual gas valve in the gas
piping to the appliance.
13. Remove the manometer from the pressure tap on top of
the gas valve. On Models 151 - 501 re-tighten the set
screw inside the pressure tap.
remove the 1/8" (3 mm) field supplied fitting and
reinstall the pipe plug removed in Step 3.
When re-tightening the set screw, be sure to
WARNING
tighten securely to prevent gas leaks.
Do not check for gas leaks with an open
flame -- use the bubble test.
use the bubble test or check for gas leaks
can cause severe personal injury, death, or
substantial property damage.
14. Turn on the gas supply at the manual gas valve.
15. Turn the power switch to the "ON" position.
16. Adjust the temperature set point on the control panel of
the SMART SYSTEM control module to the desired
water temperature so the appliance will call for heat.
125
150
175
200
N/A
N/A
N/A
N/A
95
86
79
74
179
164
149
138
369
333
308
287
564
513
472
441
1100
974
871
820
1700
1540
1400
1300
3000
2720
2500
2340
6150
5640
5130
4720
On Models 601 - 801
Failure to
23