Setting up a PROFIBUS network
2-5-4

Shielding Precautions

Cable Shield Connection
Inside cabinet
Ground Rail
Outside cabinet
To ensure electro-magnetic compatibility (EMC), the shield of the cable
should be connected to the metal case of the plug connector.
When entering the control cabinet in which the PRT1-SCU11 Unit is installed,
the bus cable shield should be brought into physical contact with a grounding
rail using a grounding clamp or similar device. The cable shield should con-
tinue in the cabinet right up to the PROFIBUS device.
Ensure that the Unit and the control cabinet in which it is mounted have the
same ground potential by providing a large-area metallic contact to ground,
e.g. galvanized steel to ensure a good electrical connection. Grounding rails
should not be attached to painted surfaces.
For further information regarding PROFIBUS network installation, please refer
to "Installation Guideline for PROFIBUS-DP/FMS" (PNO Order No. 2.112),
which is available at every regional PROFIBUS Organization. The information
covers:
• Commissioning of PROFIBUS equipment.
• Testing the PROFIBUS cable and bus connectors.
• Determining loop resistance.
• Testing for correct bus termination.
• Determining the segment length and cable route.
• Other test methods.
• Example of an equipment report in the PROFIBUS guideline.