Connection For E5Er/E5Ar Compoway-F Communications - Omron PRT1-SCU11 Operation Manual

Profibus-dp gateway to host link/compoway-f
Hide thumbs Also See for PRT1-SCU11:
Table of Contents

Advertisement

Wiring the RS-422/RS-485 Devices
PRT1-SCU11
RS-485
FG
R-
R+
Terminator 220
W(1/2 W)
2-3-5

Connection for E5ER/E5AR Compoway-F Communications

Shield
23
(R+)
23
24
24
(R-)
E5ZN
(No.0,1,2)
The E5ER / E5AR Temperature Controllers all use Compoway-F communica-
tions over 2-wire RS-485.
• The RS-485 connection can be either one-to-one or one-to-N. Up to 15
Temperature Controller units can be connected in a one-to-N system.
• The total cable length is 500 m max.
The figure below shows the connection between one PROFIBUS-DP Gate-
way Unit and 1 to 15 E5ER / E5AR Temperature Controller Units. Refer to the
E5ER / E5AR User Manuals for more information on Wiring.
PRT1-SCU11
RS-485
FG
R-
R+
Shield
(R+)
(R-)
E5ZN
(No.3,4,5)
(No.13,14,15)
E5ER / E5AR side
RS-485
E5ER E5AR
Terminator
220
(1/2 W
Shield
Section 2-3
Terminator
220 Ω(1/2 W)
(R+)
23
24
(R-)
E5ZN
Pin No.
Description
1
1
R-
2
2
R+
E5ER / E5AR side
RS-485
End Node
Pin No.
Description
E5ER E5AR
2
2
R−
1
1
R+
Use a 220 Ω (1/2 W)
terminator.
25