5. EMI And Environmental Type Tests

5. EMI And Environmental Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 60255-5
IEC 60255-5
a
RuggedCom-specified severity levels
Table 5.1. IEC 61850-3 EMI Type Tests
RuggedCom® RuggedBackbone™
Description
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Conducted) RFI
Magnetic Field
Voltage Dips & Interrupts
Damped Oscillatory
Mains Frequency Voltage
Ripple on D.C.
Power Supply
Dielectric Strength
H.V. Impulse
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal ports
D.C. Power ports
Earth ground ports
Signal ports
D.C. Power ports
Signal ports
D.C Power ports
Earth ground ports
Enclosure Ports
D.C. Power ports
Signal ports
D.C. Power ports
Signal ports
30V Continuous, 300V for 1s
D.C. Power ports
30V Continuous, 300V for 1s
D.C. Power ports
Signal ports
2kVAC (Fail-Safe Relay output)
D.C. Power ports
Signal ports
5kV (Fail-Safe Relay output)
D.C. Power ports
40
RX1512 Installation Guide Rev 105
Test Levels
+/- 8 kV
+/- 15 kV
20 V/m
+/- 4kV @ 2.5kHz
+/- 4kV
+/- 4kV
+/- 4kV line-to-earth,
+/- 2kV line-to-line
+/- 2kV line-to-earth,
+/- 1kV line-to-line
10V
10V
10V
40 A/m, continuous,
1000 A/m for 1 s
1000 A/m for 1 s
30% for 0.1s, 60% for
0.1s, 100% for 0.05s
2.5kV common, 1kV
diff. mode@1MHz
2.5kV common, 1kV
diff. mode@1MHz
10%
2kVDC
5kV
Severity
Levels
4
4
a
Note
a
Note
4
4
4
3
3
3
3
a
Note
5
N/A
3
3
4
4
3
N/A
N/A
N/A
N/A