Ieee 1613 Type Tests; Iec Environmental Type Tests; Table 17 - Ieee 1613 Type Tests; Table 18 - Environmental Type Tests - RuggedCom RuggedSwitch RS900L Installation Manual

8-port managed switch with eovdsl uplinks
Table of Contents

Advertisement

5.2 IEEE 1613 Type Tests

Test
IEEE C37.90.3
ESD
IEEE C37.90.2
Radiated RFI
IEEE C37.90.1
Fast Transient
IEEE C37.90.1
Oscillatory
IEEE C37.90
H.V. Impulse
Dielectric
IEEE C37.90
Strength

Table 17 - IEEE 1613 Type Tests

NOTE:
If the unit contains copper ports the IEEE 1613 conformance is Class 1 (During disturbance errors may occur
but recovery is automatic).
If the unit contains all fiber ports the IEEE 1613 conformance is Class 2 (During disturbance no errors will
occur).

5.3 IEC Environmental Type Tests

Test
IEC 60068-2-1
Cold Temperature
IEC 60068-2-2
Dry Heat
Humidity (Damp Heat,
IEC 60068-2-30
IEC 60255-21-1
Vibration
IEC 60255-21-2

Table 18 - Environmental Type Tests

©
2007 RuggedCom Inc. All rights reserved
All manuals and user guides at all-guides.com
Description
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
D.C. Power ports
A.C. Power ports
Earth ground ports
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
Description
Test Ad
Test Bd
Test Db
Cyclic)
Tests Fc
Shock
Tests Ea
25
Test Levels
+/- 8kV
+/- 15kV
35 V/m
+/- 4kV @ 2.5kHz
+/- 4kV
+/- 4kV
+/- 4kV
2.5kV common mode @ 1MHz
2.5kV common & differential mode @ 1MHz
2.5kV common & differential mode @ 1MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2kV AC(Failsafe Relay)
2kV AC
2kV AC
Test Levels
-40 deg. C, 16 Hours
+85 deg. C, 16 Hours
95% (non-condensing), 55°C, 6 cycles
2g @ (10-150) Hz
30g @ 11 ms
Severity
Levels
N/A
N/A
N/A
Class 2
Class 2
Rev101

Advertisement

Table of Contents
loading

Table of Contents