Ieee 1613 Type Tests; Iec Environmental Type Tests - RuggedCom RuggedSwitch RS969 Installation Manual

Table of Contents

Advertisement

3.7 IEEE 1613 Type Tests

IEEE Test
IEEE 1613
Clause
C37.90.3
9
C37.90.2
8
C37.90.1
7
C37.90.1
7
C37.90
6
C37.90
6
NOTES:
If the unit contains copper ports the IEEE 1613 conformance is Class 1 (During disturbance errors may occur but
recovery is automatic).
If the unit contains all fiber ports the IEEE 1613 conformance is Class 2 (During disturbance no errors will occur).

3.8 IEC Environmental Type Tests

Test
IEC 60068-2-1
Cold Temperature
IEC 60068-2-2
Humidity (Damp Heat,
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
IEC 60529 (IPx6)
Ingress Protection
IEC 60529 (IPx7)
Ingress Protection
IEC 60529 (IP6x)
Ingress Protection
©
2008 RuggedCom Inc. All rights reserved
Description
Enclosure Contact
ESD
Enclosure Air
Radiated RFI
Enclosure ports
Signal ports
D.C. Power ports
Fast Transient
A.C. Power ports
Earth ground ports
Signal ports
Oscillatory
D.C. Power ports
A.C. Power ports
Signal ports
H.V. Impulse
D.C. Power ports
A.C. Power ports
Signal ports
Dielectric Strength
D.C. Power ports
A.C. Power ports
Description
Test Ad
Dry Heat
Test Bd
Test Db
Cyclic)
Vibration
Tests Fc
Shock
Tests Ea
Water Jet
Water Submersion
Dust Talcum
2.5kV common mode @ 1MHz
2.5kV common & differential mode @ 1MHz
2.5kV common & differential mode @ 1MHz
-40 deg. C, 16 Hours
+85 deg. C, 16 Hours
95% (non-condensing), 55°C, 6 cycles
2g @ (10-150) Hz
30g @ 11 ms
100l/m @ 2.5m as per 14.2.6
30 min @ 1m as per 14.2.7
2kg/m3 for 8h as per 13.4
23
Test Levels
+/- 8kV
+/- 15kV
35 V/m
+/- 4kV @ 2.5kHz
+/- 4kV
+/- 4kV
+/- 4kV
5 kV (Failsafe Relay)
5 kV
5 kV
2kV AC(Failsafe Relay)
2kV AC
2kV AC
Test Levels
Rev104
Severity
Levels
N/A
N/A
N/A
Class 2
Class 2
N/A
N/A
Cat. 1&2