Technical Data

Call for heat priority logic table
The Vitodens 100-W, WB1B boiler has several operating control options. The following table provides the priority levels of
each of the different operating controllers.
Priority
Control operating mode
1
Freeze protection
2
Open Therm
3
DHW / external heat demand
4
Outdoor temperature sensor
5
0-10 VDC
6
Room thermostat (RT terminal)
*1
Boiler control will adjust the boiler water temperature set-point to the highest of all input signals.
*2
Priority #5 (outdoor temperature sensor / RT contact) not functional when 0-10V DC or OT inputs are recognized by the boiler control.
74
Required signal
*1
Boiler temperature <5ºC / 41ºF
OT signal
Close DHW contact in power / pump
module
- boiler set-point temp. = 78ºC (non-
adjustable)
*2
- Temperature dial "tr"setting
- RT contact closed or OT
connection terminals 1 & 2 shorted.
0-10 VDC signal.
Close RT contact in power / pump
module.
Pump output
Pump off delay
On
4 minutes / 240
seconds
On
20 seconds
On
20 seconds
On
4 minutes / 240
seconds
On
20 seconds
On
4 minutes / 240
seconds