Necessary Tools - Viessmann VITODENS 100-W Installation And Service Instructions Manual

Wall-mounted, gas-fired condensing boiler heating input 37 to 118 mbh 10.8 to 34.5 kw
Hide thumbs Also See for VITODENS 100-W:
Table of Contents

Advertisement

Start-up, Inspection and Maintenance

Necessary Tools

40
Special items
H Approved leak detection fluid for
natural gas
H Pipe joint sealant
H Garden hose for pressure testing
Testing/analysis equipment
H Multimeter to measure
0 - 12 A, 120 V and Ω resistances
H Flue gas analyzer to measure % CO
or O
(i.e. Bacharach fluid samplers
2
or suitable electronic flue gas
analyzer)
H Manometer to measure gas pressure
0 to 11 "w.c. (accurately) and up to
28 "w.c. gas pressure (or a
non-electric Magnehelic® manometer
may also be utilized)
H Stack thermometer 0 to 500 °F /
0 to 260 °C
H Bacharach calculator or suitable
tables to calculate standard
(non-condensing) efficiency
H Carbon monoxide measuring
equipment 0 to 400 ppm.
Cleaning supplies
H Plastic hand brush
H Rags
Use only calibrated equipment.