RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
• Downloading via Phone Line or Internet: By phone line via an IBM compatible computer, Compass downloading software, and a compatible HAYES or CIA modem specified by Honeywell. By Internet via an appropriate communications device (ex. 7845i-GSM) and Compass downloading software. This allows site maintenance independent of central station monitoring, and modification to sites globally via the Internet.
Installation and Setup Guide Important Installation Highlights (Installer Please Read) • This system uses addressable keypads and Relay Modules (see table of addresses in Programming Overview section). • Keypads must be set for addresses 16-23 (first keypad is address 16, which is different from previous controls) and programmed in data fields *190-*196.
Installation Instructions Mounting Board with RF Receiver 1. a. Remove the receiver board from its case, then insert the top of the board into the slots at the top of the cabinet, as shown in Detail A in Figure 3. Make sure that the board rests on the correct row of tabs. b.
Mounting and Wiring the Control Wiring to Keypads 1. Connect keypads to the keypad terminals as shown on the Summary of Connections diagram. Determine wire size using the Wire Run Chart below. 2. Set keypad addresses. Refer to the address setting instructions included with the keypads and set each keypad device address according to the Keypad Addresses table below.
Installation Instructions Sounder (Bell) Connections EXTERNAL ALARM 1. Make sounder connections to alarm output TERMINALS ON CONTROL BOARD SOUNDER terminals 3 (+) and 4 (–). For supervised output, continue with steps 2 and 3. 2000 2. Cut the red Bell Supervision Jumper located ALARM OBSERVE OUTPUT...
Mounting and Wiring the Control CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE 24-HOUR BATTERY BACKUP REQUIREMENTS The California State Fire Marshal and UL have regulations which require that all residential fire alarm control panels must be provided with a backup battery which has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the intended standby condition, followed by at least 4 minutes in the intended fire alarm signaling condition.
Installation Instructions Hardwire Zones Normally Open Zones/ Normally Open EOLR Zones 1. Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across the loop wires at the last device. 2. Enable normally open/EOLR zones using Zone Programming mode, “Hardwire Type” prompt. Normally Closed Zones/Normally Closed EOLR Zones 1.
Mounting and Wiring the Control Installing the RF Receiver You can use any ADEMCO 5800 Series Wireless Receivers, including: RF Receiver No. of Zones 5881L/5882L up to 8 5881M/5882M up to 16 (transmitter zone numbers = 9-24; button zone numbers = 49-56) up to 16 (transmitter zone numbers = 9-24;...
Installation Instructions Installing the Transmitters 1. To be sure reception of the transmitter's signal at the proposed mounting location is adequate, perform a Go/No Go Test, described in the Testing the System section. 2. Install transmitters in accordance with the instructions provided with each. 3.
Mounting and Wiring the Control 5-PIN TRIGGER CONNECTOR A UL Listed keyswitch is required for fire installations and UL commercial and residential burglar alarm installations. If a keyswitch is used on: • an installation that transmits opening and closing 4-WIRE 4146 KEYSWITCH CABLE signals, the keyswitch zone must be programmed to...
Installation Instructions On-Board Triggers 5-PIN TRIGGER CONNECTOR Connect field wiring to the desired trigger pin on the 8-pin trigger connector centrally located above the terminal strip. You can use a 4-wire cable as shown. If on-board triggers are used, the wiring between the control unit and the UL Listed device must be run in conduit, be no more than 3 feet apart and have no intervening barriers or walls.
Mounting and Wiring the Control The 4286 modules is UL Listed only for use on residential fire and UL residential burglar alarm installations. Phone Module Problems If no touch tones are produced following access to the security system from on-premises (this problem may arise in rare cases), it may be necessary to reverse the wires connected to terminals 3 and 4 on the phone module and the wires connected to terminals (21) &...
Installation Instructions Audio Alarm Verification Connections (AAV, “listen-In”) Using the UVS System with UVCM Module Refer to the connection diagrams below. One diagram shows connections when a 4286 Phone Module is used, the other shows connections when the 4286 is not used. Connections use one of the on-board triggers.
Page 19
Using the AVS System with AVS Module and AVST Remote Stations The AVS system provides audio alarm verification via the phone line. To use the AVS with this control, the AVS must be set for non-addressable mode by setting the module to address 31.
Installation Instructions Wiring the AVS to the Control The AVS Base unit board has several terminal blocks for making connections to remote stations, telephone lines, and to the control panel. Refer to the diagram below and the instructions provided with the module. RING RJ31X RING...
User Security Codes The system supports up to 16 security codes, which can each be assigned one of 4 authority levels. The authority level determines the functions each code can perform as follows: Authority Levels (authority levels can be assigned to users 3-16 only; users 1 and 2 cannot be changed) Level User No.
Installation Instructions Keypad Functions The following is a brief list of system commands. For detailed information, see the User's Manual. Voice Keypads (refer to the User Guide for specific procedures for activating and using these features) The 6150V/6160V Voice Keypads provide the following features: •...
S E C T I O N Testing the System • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Test Procedures After the installation is complete, you should perform the following tests: System Test:...
Installation Instructions NOTES: • All BR type units must physically be activated to clear the display. • When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other buttons on that transmitter are cleared. This also applies to 5816 and 5817 transmitters, which have multiple loops (zones).
S E C T I O N Regulatory Agency Statements • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • “FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 15 STATEMENT”...
Page 28
Installation Instructions Industrie Canada AVIS: l’étiquette d’Industrie Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme aux normes de protection, d’exploitation et de sécurité des réseaux de télécommunications, comme le prescrivent les documents concernant les exigences techniques relatives au matériel terminal.
S E C T I O N Limitations and Warranty • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or...
Page 30
Installation Instructions WARNING THE LIMITATIONS OF THIS ALARM SYSTEM (Continued) The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working properly. The security keypad (and remote keypad) should be tested as well.