Water pressure in the central heating system

Message ' Water pressure
too low' on your RS100
thermostat.
On the display of the RS100
a low water pressure can
be indicated. For further
information see the relevant
user manual.
The installation will function optimally with a water
pressure of between 16 and 18 PSI (1.1 and 1.3
bar).
If the water pressure drops below 12 PSI (0.8 bar),
the display will show FILL. During this message
the boiler will remain functioning at a reduced
level. After replenishing the system (see following
chapter) just above 22 PSI (1.5 bar) the message
FILL will disappear and the boiler will function
normally again.
When the water pressure drops below 10 PSI (0.7
bar), the display will show a flashing FILL text.
The boiler will shut down and will function normally
again after replenishing the system to just above
22 PSI (1.5 bar).
To retreive the water pressure on the display from
the Good reading:
-
Press the Step key once briefly.
The water pressure will be shown.
Press the Step key briefly to return to the Good
reading.
Water pressure is too high (>42 PSI / 3 bar), if
HIGH indication remains continuously visible, the
boiler is taken out of operation. The installation
pressure needs to be decreased by draining water
until the pressure is between 16 and 18 PSI (1.1
and 1.3 bar).