Hoshizaki KML "F" SERIES Service Manual page 42

Kml “f” series, kml “h” series modular crescent cuber
Table of Contents

Advertisement

Dip Switch
No. 5
OFF
ON
OFF
ON
5) Freeze Timer
Adjust to proper specification, or the unit may not operate correctly.
Two new dip switches numbered 9 and 10 have been added to the improved "E"
board to better prevent possible freeze ups. These settings come factory set to the
default setting of 60 min. (OFF, OFF). Check the adjustment chart published in the
Tech Specs for proper settings. If the old board does not have these two dip switches,
(only 8 instead of 10), leave setting as OFF, OFF.
Dip Switch
No. 9
OFF
ON
OFF
ON
6) Bin Control
MODELS WITH THERMOSTAT
When the ambient temperature is below 45°F, the Bin Control Thermostat
operates to stop the icemaker even if the Ice Storage Bin is empty. When
the Thermostat is set in the prohibited range, the icemaker operates
continuously even if the Ice Storage Bin is filled with ice. Setting in the
prohibited range might cause severe damage to the icemaker resulting in
failure.
No adjustment is required under normal use, as the Bin Control is factory-adjusted.
Adjust it, if necessary, so that the icemaker stops automatically within 10 seconds after
ice contacts the Bin Control Thermostat Bulb.
SETTING
Dip Switch
No. 6
OFF
OFF
ON
ON
CAUTION
SETTING
Dip Switch
No. 10
OFF
OFF
ON
ON
CAUTION
FREQUENCY
every cycle
every 2 cycles
every 5 cycles
every 10 cycles
TIME
60 min.
70 min.
50 min.
60 min.
42