Condensing gas boiler engineering submittal sheet

Advertisement

GB162-80
Condensing Gas Boiler
Performance Data
Gas input
Gross rated output
IBR Rating
Boiler horsepower
AFUE
General Data
Boiler category
Heat exchanger construction
Maximum allowable working pressure
Water content
Weight - shipping (approx.)
Weight - operating (approx.)
Standard relief valve size (inlet x outlet)
Standard relief valve pressure rating (other capacities available upon request)
Venting category
Operational Data
Maximum supply water temperature
Minimum return water temperature
Electrical Data
Electrical voltage mains
Power consumption max load (without pump group)
Power consumption partial load (without pump group)
Max. permissible fuse rating
2 of 6
Bosch Thermotechnology Corp. reserves the right to make changes without notice due to
continuing engineering and technological advances | BTC 432008101 C | 04.2012
Engineering Submittal Sheet
Unit
MBtu/h
MBtu/h
MBtu/h
H.P
%
Unit
PSIG
Gallons
Lbs
Lbs
Inch
PSI
Unit
°F
°F
Unit
V AC
Watts
Watts
Amps
Bosch Thermotechnology Corporation
Londonderry, NH • Ft. Lauderdale, FL • Irvine, CA
Tel: 1-800-283-3787 Fax: 1-603-965-7581 www.buderus.us
Value
290
260
226
7.7
93.8
Value
Condensing
Aluminum
58
1.30
189
200
¾
¾
x
30
IV
Value
180
< 40° F Supply
Value
120
104
29
15