T8600D, T8601D AND T8602D CHRONOTHERM
THERMOSTAT
RC
Y
G
O
2
4
COMPRESSOR
COOL
CONTACTOR
DAMPER
FAN
RELAY
L1
(HOT)
L2
1
COOLING
TRANSFORMER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A
ONE TRANSFORMER SYSTEM.
3
CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT
PUMP SYSTEMS.
4
AVAILABLE ON SELECT MODELS. OT WIRES MUST HAVE A
SEPARATE CABLE FROM THE THERMOSTAT CABLE.
5
T8600D MODELS REQUIRE POWER TO R TERMINAL AT ALL TIMES.
Fig. 17. Typical hookup of T8600 or T8602 in heat and
cool system with two transformers.
THERMOSTAT
C
G
W
R
2
HEAT
RELAY
FAN
RELAY
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
NOT AVAILABLE ON "A" MODELS.
Fig. 18. Typical hookup of T8601 in heat only application.
®
B
W
R
OT
OT
4
5
HEAT
3
RELAY
OUTDOOR
TEMPERATURE
SENSOR
HEAT
DAMPER
3
1
L1
(HOT)
L2
HEATING
TRANSFORMER
M10348
1
L1
(HOT)
L2
TRANSFORMER
M10357
IV DELUXE PROGRAMMABLE THERMOSTATS
C
Y
G
COMPRESSOR
CONTACTOR
FAN
RELAY
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT
PUMP SYSTEMS.
3
AVAILABLE ON SELECT MODELS. OT WIRES MUST HAVE A
SEPARATE CABLE FROM THE THERMOSTAT CABLE.
Fig. 19. Typical hookup of T8601 in heat
and cool system with one transformer.
RC
Y
G
2
COMPRESSOR
CONTACTOR
FAN
RELAY
L1
(HOT)
L2
1
COOLING
TRANSFORMER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A
ONE TRANSFORMER SYSTEM.
3
CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT
PUMP SYSTEMS.
4
AVAILABLE ON SELECT MODELS. OT WIRES MUST HAVE A
SEPARATE CABLE FROM THE THERMOSTAT CABLE.
5
T8601D MODELS REQUIRE POWER TO R TERMINAL AT ALL TIMES.
Fig. 20. Typical hookup of T8601 in heat
and cool system with two transformers.
25
THERMOSTAT
O
B
W
R
3
HEAT
COOL
2
RELAY
DAMPER
OUTDOOR
TEMPERATURE
SENSOR
HEAT
DAMPER
2
TRANSFORMER
THERMOSTAT
5
O
C
B
4
W
R
HEAT
COOL
RELAY
DAMPER
OUTDOOR
TEMPERATURE
3
SENSOR
HEAT
DAMPER
3
HEATING
TRANSFORMER
OT
OT
3
1
L1
(HOT)
L2
M10353
OT
OT
4
1
L1
(HOT)
L2
M10354
68-0164—1