Weil-McLain Ultra Manual page 23

Gas-fired water boilers – series 3
Table of Contents

Advertisement

-
gas
fired water boiler
Install water piping
Figure 22
Pipe sizing and head losses for DHW
applications
(H1=Ultra boiler head loss;
H2=piping head loss)
Flow
Temp
Pipe
rate
rise
size
GPM
°F
Inches
Ultra-80 (71,000 Btuh output)
3.5
41
1
(min)
7
20
1
9
16
1
10
14
Ultra-105 (94,000 Btuh output)
4.5
42
1
(min)
7
27
1
9
21
1
10
19
13
14
Ultra-155 (139,000 Btuh output)
7.0
40
(min)
9
31
10.0
28
13
21
16
17
Ultra-230 (207,000 Btuh output)
10
41
(min)
13
32
16
26
21
20
Ultra-310 (289,000 Btuh output)
14.5
40
(min)
18
32
21.5
27
29
20
Part number 550-100-066/0608
— Boiler Manual
(continued)
H1
H2
Boiler head
Piping head
loss
loss
Feet w.c.
Feet w.c.
1.4
0.8
6.6
2.7
11.6
4.2
14.6
2.5
3.1
1.2
7.0
2.7
11.2
4.2
13.6
2.5
22.2
3.9
3.6
1.3
6.2
2.1
7.7
2.5
13.3
3.9
20.5
5.7
5.9
2.5
9.4
3.9
13.7
5.7
22.0
4.2
4.6
2.1
6.5
2.9
9.2
4.4
15.5
7.4
Figure 23
Pump curves for typical circulators suggested for DHW
loop
23