Start the boiler

Follow the
to start the boiler.
Section 7c
See
Check system and boiler
Check system piping for leaks.
1.
boiler and repair immediately.
Vent air from system
2.
the system will interfere with circulation and cause
heat distribution problems and noise.
Inspect vent system
3.
deterioration from corrosion, physical damage or
sagging. In addition — Check for gas-tight seal at
every connection and seam.
34
Start-up — operate boiler
DO NOT
proceed with boiler
operation unless boiler and
system have been filled with
water and all instructions
and procedures of previous
manual sections have been
completed. Failure to do so
could result in severe personal
injury, death or substantial
property damage. Before start-
ing the boiler, do the follow-
ing:
Section 9
• Read manual
Operating instruction
the
procedure applicable for
the gas valve supplied on
the boiler (Section
• Verify the boiler and system
full of water
are
.
Start-up prepa-
• Verify the
procedures of
ration
tion 7
have been complet-
ed.
Operating instructions
from Section
if boiler fails to start.
If found, shut down
using manual vents. Air in
thoroughly for signs of
and
9c
).
Sec-
9c
Check around the boiler
4.
procedure of Section
Verify operation
5.
procedure in Section
and service certificate
If you discover evidence of any
gas leak, shut down the boiler
at once. Find the leak source
with bubble test and repair im-
mediately. Do not start boiler
again until corrected. Failure
to comply could result in se-
vere personal injury, death or
substantial property damage.
Eliminate all system leaks.
Continual fresh makeup water
will reduce boiler life. Minerals
can build up in sections, reduc-
ing heat transfer, overheating
cast iron, and causing section
failure.
Glycol or antifreeze leaks
around the boiler may result
in fire, causing severe personal
injury, death or substantial
property damage.
p e t r o l e u m -
D o not us e
based cleaning or sealing
compounds
in boiler system.
Severe damage to boiler will
occur, resulting in substantial
property damage.
Venting system must be
sealed gas-tight
to prevent
flue gas spillage and carbon
monoxide emissions which
will result in severe personal
injury or death.
for gas odor following the
7a
of this manual.
7b
per Section
. Perform check-out
8
Installation
, and fill in the
on the same page.