Prepare Wall Penetrations - Lochinvar Shield SNR150-100 Installation & Service Manual

Commercial
Hide thumbs Also See for Shield SNR150-100:
Table of Contents

Advertisement

3
Sidewall direct venting
Figure 3-3B Alternate Clearance to Forced Air Inlets w/
Field Supplied Fittings
7' MIN. ABOVE ANY
PUBLIC WALKWAY

Prepare wall penetrations

1.
Use the factory supplied wall plate as a template to locate
the vent and air intake holes and mounting holes.
Air pipe penetration:
a.
Cut a hole for the air pipe. Size the air pipe hole as
close as desired to the air pipe outside diameter.
Vent pipe penetration:
a.
Cut a hole for the vent pipe. For either combustible
or noncombustible construction, size the vent pipe
hole with at least a 1/2 inch clearance around the
vent pipe outer diameter:
• 4½ inch hole for 3 inch vent pipe
• 5½ inch hole for 4 inch vent pipe
Drill 3/16" diameter holes for inserting the plastic anchors
into the wall.
2.
For Polypropylene Only: Install the vent and air intake
sidewall adapters from Table 2F on page 21 into the vent
plate. Slide the sidewall retaining bracket down the
sidewall adapters flush to the vent plate (FIG. 3-4B).
3.
For PVC/CPVC Only: Install the vent and air intake
piping through the wall into the vent plate openings.
Use RTV silicone sealant to seal the air pipe. Use the
cement/primer listed in Table 2D on page 20 to seal the
vent pipe.
4.
Mount and secure the vent plate to the wall, using stainless
steel screws.
5.
Seal all gaps between the pipes and wall. Seal around the
plate to the wall assuring no air gaps.
6.
Assemble the vent cap to the vent plate (see FIG.'s 3-4A
and 3-4B). Insert the stainless steel screws into the vent
cap screw hole openings and securely attach the vent cap
to the vent plate.
7. Seal all wall cavities.
8. PVC/CPVC terminations are designed to accommodate
any wall thickness of standard constructions per the
directions found in this manual.
9. Stainless steel terminations are designed to penetrate
walls with a thickness up to 9.25 inches of standard
construction.
(continued)
Figure 3-4A PVC/CPVC Sidewall Termination Assembly
IF LESS
THAN 10'
36"
MIN.
FORCED AIR
INLET
BIRD
VENT PIPING
SCREEN
(TYPICAL)
WALL PLATE
Table 3B Sidewall Vent Centerline Dimensions
Model
151 - 200
Figure 3-4B Polypropylene Sidewall Termination Assembly
SIDEWALL
ADAPTER
(VENT)
Installation & Service Manual
TM
AIR PIPING
GALVANIZED
THIMBLE
Air
Vent
3"
3"
286
4"
4"
SIDEWALL
ADAPTER
(AIR)
GALVANIZED
THIMBLE
VENT
AIR
CENTERLINE WIDTH
VENT PLATE
VENT CAP
Centerline Width
5 5/8"
5 5/8"
WALL
PLATE
SIDEWALL
RETAINING
PLATE
VENT
PLATE
VENT
CAP
IMG00085
25