wall Shield requirements for common installations
A
B
B
C
E
fig. 22 parallel installation, vertical chimney connector,
two wall shields. Reduced clearances for both rear and side
walls. Wall shields may meet at corner if desired. Shielding for
connector is centered behind connector.
ST629
Encore
wall shield
02/01
A
A
B
C
fig. 24 parallel installation with rear wall pass-through,
two wall shields. Reduced clearances to both rear and side
walls. Wall shields may meet at corner if desired. Shielding for
ST630
Enc
connector is centered behind connector. Wall pass-through
Wall shield
must comply with codes. (See "Special Installations")
B
02/01
E
A
A
C
B
B
D
E
fig. 26 corner installation, vertical chimney connector,
with rear, stove, connector and wall shields. Wall shields
ST631
Encore
MUST meet at corner. Connector heat shield extends 28"
Wall shield
(710 mm) above flue collar. A 24" (610 mm) diameter ceiling
C
02/01
heat shield must surround the chimney and be suspended 1"
(25 mm) from ceiling.
16
A = 30" (762 mm)
B = 48" (1219 mm)
C = 66" (1676 mm)
D = 36" (914 mm)
E = 1" (25 mm)
D
E
A = 48" (1219 mm)
B = 36" (914 mm)
C = 1" (25 mm)
B
C
ST630
A = 29" (737 mm)
E
B = 45" (1143 mm)
C = 16" (406 mm)
D = 36" (914 mm)
E = 1" (25 mm)
D
E
ST631
E
C
E
ST628
fig. 23 parallel installation, vertical chimney connector,
with stove, connector and wall shields. Maximum reduction
for both rear and side wall. Wall shields may meet at corner if
desired. A heat shield 24" (610 mm) in diameter suspended 1"
(25 mm) below the ceiling must surround the chimney.
D
C
F
fig. 25 parallel installation with rear wall pass-through with
stove, connector and wall shields. Wall shields may meet at
corner if desired. Connector shield extends 28" (710 mm) above
flue collar, or to the elbow whichever is less. Height "D" must be
66" (1676 mm) or reach the thimble. Pass-through must comply
with codes. (See "Special Installations".)
E
C
D
E
fig. 27 corner installation, vertical chimney connector,
two wall shields. Reduced side clearances. Wall shields
MUST meet at corner.
A = 30" (762 mm)
A
E
B = 44" (1118 mm)
C = 36" (914 mm)
D = 66" (1676 mm)
B
B
D
E = 1" (25 mm)
E
ST629a
Encore
wall shield AA
02/01
A = 30" (762 mm)
B = 23" (584 mm)
C = 44" (1118 mm)
A
B
D = 66" (1676 mm)
C
E = 36" (914 mm)
E
F = 1" (25 mm)
F
ST630a
Encore
Wall shield
BB
02/01
A = 29" (737 mm)
E
B = 45" (1143 mm)
C = 16" (406 mm)
A
A
D = 36" (914 mm)
E = 1" (25 mm)
B
B
D
E
ST631a
Encore
Wall shield
CC
02/01
ST629a
ST630a
ST631a
2000956