Weil-McLain EG Manual page 31

Gas-fired boilers – series 4
Hide thumbs Also See for EG:
Table of Contents

Advertisement

EG
PEG
EGH
Service and maintenance
❏ Service . . . . . . . . . .
Gauge glass (steam boilers)
Normal waterline is halfway up gauge
glass. Clean when needed.
1. Close lower gauge cock.
2. Open pet cock.
3. Open lower gauge cock and allow a small amount
of water to flush out through open pet cock.
4. Close pet cock.
5. Open lower gauge cock.
Boiler pressure must be low to eliminate
potential of severe burns.
If gauge glass breaks, close both gauge
cocks. Replace gauge glass. Do not replace
with thin glass tubing. Failure to comply
could cause severe personal injury, death
or substantial property damage.
❏ Start-up . . . . . . . . . .
1. Perform "Start-up" procedures in this manual,
pages 24–27, including"Verify operation"of burners
and vent damper on page 26.
2. C
eck gas piping, per pages 22 and 24, verifying no
h
indications of leakage and all piping and connec-
tions are in good condition.
3. Read the "Lighting Instructions" in the Control
Supplement.
4. Start the boiler following the "Lighting Instructions."
❏ Check/test . . . . . . . . . .
Gas piping
1. Sniff near floor and around boiler area for any in-
dication of a gas leak.
2. Test gas piping using bubble test, per page 22 of this
manual, if there is any indication of a leak.
Boiler waterline
Normal waterline is halfway up gauge glass.
Limit controls
1. Inspect and test the boiler limit control. Verify op-
eration by turning control set point below boiler
pressure. Boiler should cycle off. Return dial to
original setting.
Part Number 550-110-639/0512
-
Gas
firEd boilErs
4 —
sEriEs
boilEr manual
(continued)
Probe-type low water cutoff (when used)
Clean probe-type low water cutoff (when used) for proper
operation.
1. Turn off power to boiler and wait 5 minutes.
2. Drain water to bottom of gauge glass.
3. Turn on power.
4. Set thermostat to call for heat. Red neon lamp on lower water cutoff
should light.
5. Wait 5 minutes. Boiler should not fire.
6. Refill boiler to correct waterline. Red lamp should go off.
7. Wait 5 minutes. Boiler should fire.
8. Return thermostat to normal setting.
Float-type low water cutoff (when used)
Clean float-type low water cutoff to clear float chamber of
sediment.
1. Open blowdown valve at bottom control.
2. Drain water into a bucket.
Scald potential. Boiler pressure must be low to avoid the
potential of severe burns from steam.
3. Check float-type low water cutoff for proper operation:
a. Turn operating control to call for heat.
b. Before water gets hot, drain to bottom of gauge glass. Boiler should shut
off after water level lowers a few inches.
c. Refill boiler to correct waterline. Boiler should come back on.
31