Connect piping - tankless heater (optional)
EG and EGH boilers for tankless heater applica-
tion are available only on special order as factory-
installed optional equipment. Standard boilers
cannot be adapted for heater use. Install a tankless
heater only in a steam boiler or forced hot water.
For correct operation, install as shown in Figure 24 (water boilers)
or Figure 25 (steam boilers).
1. Automatic mixing valve must be installed per mixing valve
manufacturer's instructions.
2. Flow regulating valve must be installed. Size according to
intermittent draw of heater as shown in following table.
3. Operating control with a small differential scale is recom-
mended. Install in temperature control tapping in heater
plate.
4. In hard water areas, it is advisable to soften cold domestic
supply water to the tankless heater to prevent lime buildup.
Figure 24
Tankless heater piping (water boiler)
Piping Connections not furnished. Use
brass plugs in tees and crosses to facilitate
cleaning in hard water areas.
Figure 25
Tankless heater piping (steam boiler)
Part Number 550-110-639/0512
-
Gas
firEd boilErs
-
4 -
sEriEs
boilEr manual
Table 10
Minimum recommended pipe sizes
Heating
Boiler Model
Number
(Note 3)
Water
EG-35
EG-40
EG-45
EG-50
EG-55
EG-65
EG-75
(Note 5)
EGH-85
(Notes 4 & 6)
EGH-95
(Note 4)
EGH-105
EGH-115
EGH-125
35-S-29
35-S-29
35-S-29
35-S-29
35-S-29
35-S-29
EG-75
35-S-29
Notes
EGH-85
35-S-29
EGH-95
35-S-29
EGH-105
35-S-29
EGH-115
35-S-29
EGH-125
35-S-29
Weil-McLain ratings based on 60 PSIG domestic water pres-
sure at heater.
1. Gallons of water per minute heated from 40°F to 140°F with
2. Continuous draw - no recovery period.
3. These single wall heat exchangers comply with National
NOTES
4. EGH-85 & 95 Standing pilot systems - no tankless option
5. EG-75 Standing pilot systems - no tankless option
6. EGH-85 Water - use one heater only.
Intermittent
Continuous
Draw GPM
Draw GPM
100°F Av.
100°F Av.
Temp. Rise
Temp. Rise
(Note 1)
(Note 2)
E-624
3.00
1.60
E-624
3.00
2.00
E-624
3.25
2.40
E-626
4.00
2.80
E-626
4.25
3.20
E-632
4.50
4.00
E-632
4.50
4.80
E-632
5.50
5.60
E-632
5.50
5.55
E-632
5.75
5.75
E-632
6.00
6.00
E-632
6.00
6.00
3.00
1.60
3.00
2.00
3.25
2.40
3.25
2.80
3.50
3.20
3.75
4.00
4.00
4.80
4.00
5.00
4.00
5.00
4.00
5.00
4.00
5.00
4.00
5.00
200°F boiler water temperature.
Standard Plumbing Code provided that:
• boiler water (including additives is practically non toxic,
having a toxicity range or class of 1, as listed in Clinical
Toxicology of Commercial Products, and
• boiler water pressure is limited to max. 30 psig by
approved water or steam relief valve.
Inlet and
Temp.
Outlet
Control
Tappings
Tapping
¹⁄₂"
³⁄₄"
¹⁄₂"
³⁄₄"
¹⁄₂"
³⁄₄"
¹⁄₂"
³⁄₄"
¹⁄₂"
³⁄₄"
¹⁄₂"
³⁄₄"
¹⁄₂"
³⁄₄"
¹⁄₂"
³⁄₄"
¹⁄₂"
³⁄₄"
¹⁄₂"
³⁄₄"
¹⁄₂"
³⁄₄"
¹⁄₂"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
³⁄₄"
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents