Page 1
PFG-6 & 7 Control Supplement Standing Pilot Boilers Controls must only be installed by a Weil-McLain distributor or other qualified installer/service technician in accordance with this Supplement and all applicable codes and requirements of the authority having jurisdiction. Read this Control Supplement completely before beginning the installation.
EGH-85 & 95 Series 4 and PFG-6 & 7 Series 6 & 7 Please read this page first! Hazard definitions The following defined terms are used throughout these instructions to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
Control Supplement — Standing Pilot Boilers Control installation — EGH-85 & 95 water boilers For your safety, turn off electrical power supply and turn off external gas supply valve before attempting to work on the boiler. Failure to comply can cause severe personal injury, death or substantial property damage.
Control Supplement — Standing Pilot Boilers Control installation — PFG-6 & 7 water boilers For your safety, turn off electrical power supply and turn off external gas supply valve before attempting to work on the boiler. Failure to comply can cause severe personal injury, death or substantial property damage. 1.
EGH-85 & 95 Series 4 and PFG-6 & 7 Series 6 & 7 Control installation — EGH-85 & 95 steam boilers Part Number 550-110-031/0605...
Page 9
Control Supplement — Standing Pilot Boilers with probe-type low water cutoff For your safety, turn off electrical power supply and turn off external gas supply valve before attempting to work on the boiler. Failure to comply can cause severe personal injury, death or substantial property damage. 1.
Control Supplement — Standing Pilot Boilers with float-type low water cutoff For your safety, turn off electrical power supply and turn off external gas supply valve before attempting to work on the boiler. Failure to comply can cause severe personal injury, death or substantial property damage. 1.
EGH-85 & 95 Series 4 and PFG-6 & 7 Series 6 & 7 Lighting instructions — Robertshaw 7000ERHC FOR YOUR SAFETY READ BEFORE LIGHTING If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Control Supplement — Standing Pilot Boilers Troubleshooting Verify proper operation after servicing Never jumper (bypass) any device except for momentary testing as outlined in troubleshooting chart below. Substantial property damage and/or severe personal injury could occur. Burner access panel must be in position during boiler operation to prevent momentary flame rollout on ignition of main flame.
Page 14
EGH-85 & 95 Series 4 and PFG-6 & 7 Series 6 & 7 Troubleshooting Chart 1: Boiler will not fire — water boilers without tankless Secure connections. Check for loose wire connections or bad relay on transformer. Check for open thermostat, LWCO, high limit, spill switch or rollout thermal fuse element contacts or check for loose wire connections.
Control Supplement — Standing Pilot Boilers Troubleshooting Chart 2: Boiler will not fire — water boilers with tankless Secure connections. Check for loose wire connections or bad combination control. Check for open thermostat, LWCO, high limit, spill switch or rollout thermal fuse element contacts or check for loose wire connections.