Connect field wiring to boiler

For your safety, turn off electrical power supply at service
entrance panel before making any electrical connections to
avoid possible electric shock hazard. Failure to do so can cause
severe personal injury or death.
Refer to the Control Supplement for additional information,
lighting instructions and control wiring diagram.
Wiring must be N.E.C. Class 1.
If rollout thermal fuse element wire supplied with boiler must
be replaced, type 200 °C wire or equivalent must be used. If
other original wiring supplied with boiler must be replaced,
use only type 105 °C wire or equivalent.
Boiler must be electrically grounded as required by National
Electrical Code ANSI/NFPA 70–latest edition.
Electrical installation must comply with:
1. National Electrical Code and any other national, state, provincial or
local codes or regulations.
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1, and any local
codes
Wiring connections
1. Boiler is shipped with controls completely wired, except spill switch and
vent damper. See wiring diagram in Control Supplement for details.
2. Installer must attach wiring diagram inside jacket door.
3. See Figure 26 for field wiring. A separate 120 VAC electrical circuit with
a fused disconnect switch (15 amp recommended) should be used for
the boiler.
Figure 26
Connect field wiring in boiler junction box as shown below. See Control Supplement for more details.
Part Number 550-110-639/0512
-
Gas
firEd boilErs
4 —
sEriEs
boilEr manual
4. A strain relief bushing and adapter must be used
at each point where wiring passes through control
case (see Figure 27) to protect wiring insulation.
5. Multiple zones — Refer to zone valve manufacturer's
literature for wiring and application. A separate
transformer is required to power zone valves. Zoning
with circulators requires a relay for each circuit.
Room thermostat
1. Connect thermostat as shown on wiring diagram
on boiler.
2. Install on inside wall away from influences of drafts,
hot or cold water pipes, lighting fixtures, television,
sunrays or fireplaces.
3. If thermostat has a heat anticipator, set heat antici-
pator in thermostat to match power requirements
of equipment connected to it. Refer to the appro-
priate Control Supplement for instructions on the
thermostat anticipator setting.
Figure 27
Provide strain relief
23