Troubleshooting by Indication on the Remote Controller
Disconnect the electronic expansion valve from the PC board and check the continuity between the
connector pins.
(Normal)
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
× : No continuity
128
1 Coil check method for the moving part of the electronic expansion valve
Pin No.
1. White
: Continuity Approx. 300
: Continuity Approx. 150
2. Yellow
3. Orange
×
Approx.
300Ω
×
4. Blue
5. Red
×
Approx.
150Ω
×
Approx.
300Ω
×
Approx.
150Ω
×
SiUS39-601
6. Brown
×
Approx.
150Ω
×
Approx.
150Ω
×