D. Vent Diagrams
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between firestops.
• ALWAYS maintain specified clearances around venting and firestop systems.
• Install firestops as specified.
Failure to keep insulation or other material away from vent pipe may cause fire.
1. Top Vent - Horizontal Termination
One Elbow
Figure 5.3
Two Elbows
H
2
Figure 5.4
12
WARNING
H
1
H
1
INSTALLED
HORIZONTALLY
Heat & Glo • Crescent II • 2083-902 Rev. G • 9/05
V
Minimum
1
Elbow only
6 in
152 mm
1 1/2 ft
457 mm
2 1/2 ft
762 mm
3 1/2 ft
1067 mm
4 1/2 ft
V
+ H
1
1
V
1
H
= 15 ft (4.6 m) Maximum
1
V
Minimum
1
2 - 90
0
elbows back
to back
6 in
1 1/2 ft
2 1/2 ft
3 1/2 ft
4 1/2 ft
V
+ H
1
H
+ H
1
V
1
H
Maximum
1
2 ft
610 mm
2 ft
610 mm
3 ft
914 mm
5 ft
1.5 m
7 ft
2.1 m
1.4 m
15 ft
4.6 m
= 38 ft (11.6m) Maximum
H
+ H
Maximum
1
2
Cannot do
152 mm
2
610 mm
457 mm
3 ft
914 mm
762 mm
5 ft
1.5 m
1067 mm
7 ft
2.1 m
1.4 m
15 ft
4.6 m
+ H
= 38 ft (11.6 m) Maximum
1
2
= 15 ft (4.6 m) Maximum
2